57
13.
Leak detection methods:
The following leak detection methods are deemed acceptable for systems containing
flammable refrigerants. Electronic leak detectors shall be used to detect flammable
refrigerants, but the sensitivity may not be adequate or may need re-calibration.
(Detection equipment shall be calibrated in a refrigerant-free area). Ensure that the
detector is not a potential source of ignition and is suitable for the refrigerant used.
Leak detection equipment shall be set at a percentage of the LFL of the refrigerant
and shall be calibrated to the refrigerant employed and the appropriate percentage of
gas (25 % maximum) is confirmed. Leak detection fluids are suitable for use with most
refrigerants but the use of detergents containing chlorine shall be avoided as the
chlorine may react with the refrigerant and corrode the copper pipework. If a leak is
suspected, all naked flames shall be removed/ extinguished. If a leakage of refrigerant
is found which requires brazing, all the refrigerants shall be recovered from the system
or isolated (by means of shut off valves) in a part of the system remote from the leak.
Oxygen free nitrogen (OFN) shall then be purged through the system both before and
during the brazing process.
14.
Removal and evacuation:
When breaking into the refrigerant circuit to make repairs or for any other purpose
conventional procedures shall be used. However, it is important that best practice is
followed since in flammability is a consideration. The following procedure shall be
adhered to:
Remove refrigerant;
•
Purge the circuit with inert gas;
Evacuate;
•
Purge again with inert gas;
•
Open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders. The
system shall be flushed with OFN to render the unit safe. This process may need to be
repeated several times. Compressed air or oxygen shall not be used for this task.
Flushing shall be achieved by breaking the vacuum in the system with OFN and
continuing to fill until the working pressure is achieved, then venting to atmosphere
and finally pulling down to a vacuum. This process shall be repeated until no
refrigerant is within the system. When the final OFN charge is used, the system shall
be vented down to atmospheric pressure to enable work to take place. This operation
is absolutely vital if brazing operations on the pipework are to take place.
Ensure that the outlet for the vacuum pump is not close to any ignition sources and
there is ventilation available.
Summary of Contents for SMARTERHOME KASHSAC80TA
Page 1: ...KOGAN SMARTERHOMETM INVERTER SPLIT SYSTEM 8 2KW REVERSE CYCLE AIR CONDITIONER KASHSAC80TA...
Page 65: ...65 NOTES...
Page 66: ...66...
Page 67: ...67...