TP-6196 5/04
32
Section 4 Controller
To save changes.
To discard changes without saving.
or
S A V E
Y E S
Now move the master switch to OFF/RESET.
n o
There are 3 options when the display says SAVE:
Press:
or
To return to the first parameter, coarse voltage adjustment, to check
or change settings before saving. See Figure 4-7.
“Yes”or “no” flashes when the up or down arrow is pressed and
then the controller exits the configuration mode. The display
returns to the runtime hours.
1 P
x x x x
x x
Figure 4-12
Save Mode (after generator set and engine adjustments)
4.6 Continuous Power Mode
Jumper
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working
on
the
generator
set.
Remove the negative (--) lead first
when
disconnecting
the
battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
WARNING
Disabling the generator set.
Accidental starting can
cause severe injury or death.
Before working on the
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.
Short circuits.
Hazardous voltage/current can cause
severe injury or death.
Short circuits can cause bodily injury
and/or equipment damage
.
Do not contact electrical
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.
A jumper across controller pins P7-1 and P7-2
maintains power to the controller at all times.
Controllers are shipped with the jumper connected for
continuous power. See Figure 4-13.
Note:
The controller is powered by the generator set
engine starting battery.
The 8.5 and 12 RES
generator
sets
are
equipped
with
factory-installed battery chargers to prevent
battery discharge.
The P7 connector has either 2 or 3 pins. Disconnecting
the jumper or moving the jumper to pins P7-2 and P7-3
allows the controller to power down automatically
48 hours after the generator set shuts down if the
generator set master switch is in the AUTO position. A
remote start signal (from a transfer switch or a remote
start/stop switch connected to controller leads 3 and 4)
or moving the generator set master switch to the RUN
position turns the controller back on.