TP-6735 7/17
53
Section 4 Controller
4.10.5 SiteTech Software
A personal computer running Kohler
r
SiteTech
t
software can be used to configure and adjust the RDC
and DC controllers. See TP-6701, SiteTech Software
Operation Manual, for PC connection and software
operation instructions.
See Figure 4-13 for the settings. Refer to TP-6701,
SiteTech Software Operation Manual, for instructions.
Appendix F contains a list of controller parameters that
can be viewed and adjusted using SiteTech. The
Access column in the table shows which parameters
can only be viewed (Read or Locked), and which
parameters can be changed using the software (Write).
SiteTech software is also used to update the firmware
on the RDC and DC controllers. See TP-6701 for
instructions.
SiteTech can be used to calibrate the voltage. See
Section 4.11.
4.11 Calibration
The controller can be calibrated for utility voltage using
using a personal computer connected to the RDC/DC
controller. Kohler
r
SiteTech
t
software is required for
calibration.
Note:
Controller firmware version 2.04 or higher is
required for calibration. See Section 4.10.3 for
instructions to check the firmware version
number.
4.11.1 Calibrate Function
The RDC/DC controller can be calibrated using
SiteTech. Measure the actual utility voltage across L1
and L2, and enter the measured value into SiteTech as
described in the following procedure. See Figure 4-14.
SiteTech Group
Parameter
Value
Equivalent
RDC
Parameter
Setting
How to Enter
Genset System Configuration
Genset System Voltage
240
Uu01
Type in
230
Uu06
Type in
Genset System Frequency
60
Uu01
Drop-down box
50
Uu06
Drop-down box
Genset Voltage Phase Connection
Single Phase
Uu01 or Uu06
Drop-down box
Genset Info
Engine Model Number
CH--740*
(14RES or 14RESL)
Ec13
Type in*
Drop-down box
CH--1000*
(20RES or 20RESL)
Ec14
Type in*
Drop-down box
Genset Model Number
14RES
14RESL
20RES
20RESL
none
Type in
Genset Serial Number
See nameplate
none
Type in
Engine Serial number
See nameplate
none
Type in
* With SiteTech versions prior to 2.3, type in CH--740 or CH--1000 with capital letters and dash exactly as shown.
Figure 4-13
Controller Setup Using SiteTech Software
Summary of Contents for 14RES
Page 2: ......
Page 6: ...TP 6735 7 17 6...
Page 16: ...TP 6735 7 17 16 Section 1 Specifications Notes...
Page 102: ...TP 6735 7 17 102 Section 6 Disassembly Reassembly Notes...
Page 108: ...TP 6735 7 17 108 Section 7 Wiring Diagrams Notes...
Page 120: ...TP 6735 7 17 120 Notes...
Page 121: ...TP 6735 7 17 121 Notes...
Page 122: ...TP 6735 7 17 122 Notes...
Page 123: ......