TP-6735 7/17
75
Section 5 Component Testing and Adjustment
5.10 Fault Shutdown Tests
Verify the operation of the generator set overspeed,
overcrank, and low oil pressure shutdowns by
performing the following tests.
If these tests are
inconclusive,
test
individual
shutdown
circuit
components (wiring harness, switch, etc.) as described
elsewhere in this section.
Hazardous voltage. Moving parts.
Will cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
are in place.
DANGER
Short circuits. Hazardous voltage/current will cause
severe injury or death.
Short circuits can cause bodily injury
and/or equipment damage
.
Do not contact electrical
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until
it cools.
WARNING
Servicing the exhaust system. Hot parts can cause
severe injury or death.
Do not touch hot engine parts. The
engine and exhaust system components become extremely
hot during operation.
5.10.1 Controller Fault Shutdown
Functions
Check the operation of the fault functions programmed
in the controller by performing the following tests. If the
controller does not operate as described, check the
controller configuration settings; see Section 4.10.1.
Also check the controller wiring and connections.
Overspeed Shutdown
The overspeed setting is factory-set and is not
adjustable.
Verify that the following
controller
configuration parameters are set correctly for your unit.
See the generator set installation manual for the
settings.
D
System voltage/frequency parameter (UU)
D
Engine configuration parameter (EC)
Open the generator set output circuit breaker before
beginning the test. (See Figure 1-1 for the circuit
breaker location.)
Connect a digital voltmeter (DVM) to measure the
output frequency. Start the generator set and manually
adjust the engine speed by moving the throttle linkage.
Note:
Be careful not to touch the hot silencer when
reaching in to adjust the throttle linkage.
Increase the engine speed (parameter 4P) to at least
115% of the rated engine speed, 69 Hz on 60 Hz models
or 58 Hz on 50 Hz models. Verify that the generator set
shuts down on an overspeed fault (OS).
If the
overspeed shutdown does not operate, the generator
set should shut down on an overfrequency fault (OF)
after approximately 5 seconds.
If the controller does not indicate an overspeed fault
(OS), check the wiring to the magnetic pickup (red and
black leads, P1-5 and P1-6). Check the magnetic
pickup resistance, air gap and voltage output; see
Section 5.9.4.
Summary of Contents for 14RES
Page 2: ......
Page 6: ...TP 6735 7 17 6...
Page 16: ...TP 6735 7 17 16 Section 1 Specifications Notes...
Page 102: ...TP 6735 7 17 102 Section 6 Disassembly Reassembly Notes...
Page 108: ...TP 6735 7 17 108 Section 7 Wiring Diagrams Notes...
Page 120: ...TP 6735 7 17 120 Notes...
Page 121: ...TP 6735 7 17 121 Notes...
Page 122: ...TP 6735 7 17 122 Notes...
Page 123: ......