TP-6255 7/06
43
Section 6 Troubleshooting
Troubleshooting Chart, continued
Problem
Reference
Corrective Action
Possible Cause
Light flicker
Voltage stability (gain) setting
Check and adjust the voltage
stability (gain) setting using the
ADC 2100.
Section 7.5.3
High generator
output voltage
Incorrect controller configuration
Check and adjust the controller
configuration parameters.
Section 7.5
p
g
Incorrect controller voltage
settings
Check and adjust the controller
voltage settings.
Section 7.5.3
Engine speed too high
Check the engine speed using
tachometer or frequency meter.
Adjust governor as necessary.
Section 4.4
Loose voltage sensing
connections
Check connections: stator leads
11 and 44 (for 1-phase models) or
leads 7, 8, and 9 (for 3-phase
models) and P15 controller
connection.
Section 8.7
SCR module
Check the wiring and connections
to the SCR module.
Check the auxiliary winding fuse
F1 (lead 55).
Replace SCR module and test
voltage.
Section 7.7
Controller
Check fuses, wiring, and
connections. Before replacing the
controller, replace the SCR
module and test voltage.
Section 7.5
Section 7.7
Section 7.11
No output
voltage
AC output circuit breaker open
Check for AC voltage on the
generator side of the circuit
breaker. If there is AC voltage on
the generator side of the breaker,
then a problem in the load circuits
is causing the line circuit breaker
to trip. Check for and correct
short circuits or overloading on
the load side before resetting the
circuit breaker.
—
Alternator or control system
Perform separate excitation
procedure to isolate the problem
to the alternator or the control
system. Then troubleshoot the
alternator or control system
components as follows.
Section 8.2
Aux. winding fuse blown (lead 55)
Replace blown fuse. If fuse blows
again, check stator.
Section 8.12
SCR module
Check auxiliary winding fuse F1
(lead 55).
Replace SCR module and test
voltage.
Section 8.12
Section 7.7
Controller
Check controller settings. Check
wiring and connections. Before
replacing the controller, replace
the SCR module and test voltage.
Section 7.5
Section 7.7
Section 7.11
Summary of Contents for 6.5-27EFOZD
Page 1: ...Marine Generator Sets Models 8 32EOZD 6 5 27EFOZD TP 6255 7 06a Service ...
Page 12: ...TP 6255 7 06 12 Service Assistance Notes ...
Page 22: ...TP 6255 7 06 22 Section 1 Specifications Notes ...
Page 28: ...TP 6255 7 06 28 Section 3 Intake and Exhaust System Notes ...
Page 62: ...TP 6255 7 06 62 Section 7 Controller Notes ...
Page 78: ...TP 6255 7 06 78 Section 8 Component Testing and Adjustment Notes ...
Page 92: ...TP 6255 7 06 92 Section 10 Wiring Diagrams Notes ...
Page 100: ...TP 6255 7 06 100 ...
Page 101: ...TP 6255 7 06 101 ...
Page 102: ...TP 6255 7 06 102 ...
Page 103: ...TP 6255 7 06 103 ...