144
TP-6694
9/20
6.1.14 Remote Reset Feature
The remote reset switch provides generator set controller resetting after a fault shutdown at a remote location. See Figure 79
and Figure 80 for user-supplied switch connection.
Press and hold the switch for 2-3 seconds and release to reset the generator set controller.
See the following subsection,
“Accessory Connections,” for terminal identifications.
Figure 79
Remote Reset Switch Connections
Switch Rating
12 volts DC minimum, 1 amp minimum
Wiring Recommendation
Gauge
m (ft.)
18-20
30.5 (100)
14
153 (500)
10
305 (1000)
Figure 80
Switch Rating & Wiring Recommendations
Battery Ground
Connect to TB1 as a Digital Input
Remote Reset Switch
Contacts Normally Open
Momentary Closed to Activate