34
TP-6694
9/20
Figure 8
AC Circuit Fuses in Control Box
Figure 9
Controller DC Fuses
1.3 Controller Logic Specifications
The controller logic specifications section is an overview of the various features and functions of the controller. Certain features
function only when optional accessories are connected. See the section titled: Operation, for details.
The default selection time delays and digital outputs are factory set and adjustable. Data entries require using a PC and
SiteTech™ software. See the SiteTech™ software operation manual for details.
Inhibit Time Delay.
The inhibit time delay is the time period following crank disconnect during which the generator set stabilizes
and the controller does not detect a fault or status event. Select the desired inhibit time delay from 0 to 60 seconds.
Time Delay (Shutdown or Warning).
The time delay follows the inhibit time delay. The time delay is the time period between
when the controller first detects a fault or status event and the controller warning or shutdown lamp illuminates. The delay
prevents nuisance alarms. Select the desired time delay from 0 to 60 seconds.
GM69407
V7/V8/V9 fuses, 1.5 Amp. (qty. 3)
GM6435-C
F1 1 Amp. auto-resettable
F2 1 Amp. auto-resettable
F3 12 Amp. non-replaceable
Summary of Contents for APM402
Page 6: ...6 TP 6694 9 20 ...
Page 16: ...16 TP 6694 9 20 ...
Page 42: ...42 TP 6694 9 20 ...
Page 78: ...78 TP 6694 9 20 ...
Page 112: ...112 TP 6694 9 20 ...
Page 120: ...120 TP 6694 9 20 ...
Page 124: ...124 TP 6694 9 20 Figure 54 20 150 kW Permanent Magnet Single Phase Alternators ADV 5875AB 1 ...
Page 125: ...TP 6694 9 20 125 Figure 55 20 300 kW Permanent Magnet Alternators ADV 5875AB 2 ...
Page 128: ...128 TP 6694 9 20 ...
Page 131: ...TP 6694 9 20 131 Figure 61 Battery Charger to Controller Connections DEC 3000 Controller ...
Page 153: ...TP 6694 9 20 153 Figure 90 Controller Wiring Connections GM78246G 1 ...
Page 154: ...154 TP 6694 9 20 Figure 91 Controller Wiring Connections GM78246G 2 ...
Page 171: ......