INSTALLATION INSTRUCTIONS

TT-1303 7/02a

--

Original Issue Date:

9/01

Model:

20--2000 kW

Market:

Industrial Generator Sets with the 550 Controller

Subject:

Remote Annunciator Alarm Kits: GM17071-KP1, GM17071-KP1S,
GM17071-KP2, GM17071-KP2S, GM17071-KP3, and GM17071-KP3S

Introduction

The remote annunciator allows the operator to monitor
the generator set condition from a remote location.
When a generator alarm condition occurs, the remote
annunciator alerts the operator through visual and
audible signals. The remote annunciator kit includes a
14-relay dry contact box to isolate the annunciator from
the controller and to protect the controller from voltage
surges and stray voltage. See Figure 1.

When a generator alarm condition occurs, the
appropriate relay contacts close to activate the horn and
corresponding lamp on the remote annunciator. Mount
the remote annunciator in a location easily observable
by operating personnel at their work stations.

Read the entire installation procedure and compare the
kit parts with the parts list in this publication before

beginning installation. Perform the steps in the order
shown. Observe applicable national and local electrical
codes when installing the wiring system.

Features

The

following

paragraphs

describe

the

remote

annunciator specific features.

Alarm Horn

Alarm Horn.

The alarm horn sounds when a fault or

prealarm condition exists, except emergency stop,
battery charger fault, or low battery voltage. Silence the
alarm horn when the generator set master switch is in
the AUTO position. The alarm horn will not silence when
the NOT IN AUTO lamp is lit.

See the installation

procedure, step 8, for the resetting instructions.

Surface-Mount Remote Annunciator

14-Relay Dry Contact Box

A-293983

A-258782

P

FBA--1

42B

10 AMP

NO

C

C

NO

C

NO

C

NO

C

NO

C

NO

C

NO

C

NO

C

NO

C

NO

C

NO

C

NO

C

NO

C

NO

K1

K2

K3

K4

K5

K6

K7

K8

K9

K10

K11

K12

K13

K14

INPUT

CONTACT RATINGS: 10A @120VAC RES. LOAD

.01A @28VDC MIN.

10A @28VDC MAX.

PCB ASSY A--320639

LOT NO.

42A

2

K1 K2

K3

K4

K5

K6

K7

K8

K9 K10 K11

K13 K14

K12

P

N

Figure 1

Remote Annunciator Alarm Panel

Summary of Contents for GM17071-KP1

Page 1: ...stations Read the entire installation procedure and compare the kit parts with the parts list in this publication before beginning installation Perform the steps in the order shown Observe applicable...

Page 2: ...temperature shuts down the generator set Line Power The lamp illuminates when commercial utility power or other source supplies the power when equipped with an auxiliary contact When the lamp illumina...

Page 3: ...pped 1 3 Disconnect the generator set engine starting battery ies negative lead first 2 Mount and connect the controller connection assembly 2 1 GM17070 KP1 and GM17070 KP1S kits 20 300 kW 2 1 1 Remov...

Page 4: ...access door 2 3 3 Attach the controller connection assembly GM13984 to the junction box inner panel studs using six spacers X 712 9 and nuts X 70 12 Place the spacers between the controller connection...

Page 5: ...location D An area as near to the generator set controller as practical 3 2 Remove the four cover screws X 6216 1 and lift the box cover 256880 to access the internal components 3 3 Mount the 14 relay...

Page 6: ...5 16 in diameter or X 283 32 1 2 in diameter as required Do not use terminals 42A and 2 on the 14 relay dry contact box terminal strip to supply voltage to the relay contacts The user must attach sep...

Page 7: ...ctrical box in the wall See Figure 8 for the mounting hole dimensions Protect the remote annunciator from dust and debris when drilling the holes Note Use mounting hardware suitable for the wall compo...

Page 8: ...total wire length for each conductor is 122 m 400 ft According to the chart in Figure 9 this example requires 14 gauge wire for leads N and 42B only Use stranded or solid 18 or 20 gauge wire for signa...

Page 9: ...Pressure RDO8 K12 Input K12 NO terminal 63 Low Water Temperature RDO5 K13 Input K13 NO terminal 35 High Engine Temperature Warning RDO6 K14 Input K14 NO terminal 40 Figure 10 Remote Annunciator Kit W...

Page 10: ...Move the remote annunciator alarm horn switch to SILENCE to stop the alarm horn The respective remote annunciator lamp remains lit 8 3 Disconnect the generator set from the system load with the line c...

Page 11: ...ing 0 688 x 0 875 in NPT X 634 11 1 Bushing 0 938 x 1 187 in NPT X 634 14 2 Rivet pop 1 8 diameter Al Al X 781 21 4 Screw 10 24 x 0 50 in X 6216 1 1 Fuse 10 amp 223316 1 Box dry contact 226676 1 Holde...

Page 12: ...1 Bushing 0 688 x 0 875 in NPT X 634 11 1 Bushing 0 938 x 1 187 in NPT X 634 14 2 Rivet pop 1 8 diameter Al Al X 781 21 4 Screw 10 24 x 0 50 in X 6216 1 1 Fuse 10 amp 223316 1 Box dry contact 226676...

Reviews: