INSTALLATION INSTRUCTIONS
TT-1303 7/02a
--
Original Issue Date:
9/01
Model:
20--2000 kW
Market:
Industrial Generator Sets with the 550 Controller
Subject:
Remote Annunciator Alarm Kits: GM17071-KP1, GM17071-KP1S,
GM17071-KP2, GM17071-KP2S, GM17071-KP3, and GM17071-KP3S
Introduction
The remote annunciator allows the operator to monitor
the generator set condition from a remote location.
When a generator alarm condition occurs, the remote
annunciator alerts the operator through visual and
audible signals. The remote annunciator kit includes a
14-relay dry contact box to isolate the annunciator from
the controller and to protect the controller from voltage
surges and stray voltage. See Figure 1.
When a generator alarm condition occurs, the
appropriate relay contacts close to activate the horn and
corresponding lamp on the remote annunciator. Mount
the remote annunciator in a location easily observable
by operating personnel at their work stations.
Read the entire installation procedure and compare the
kit parts with the parts list in this publication before
beginning installation. Perform the steps in the order
shown. Observe applicable national and local electrical
codes when installing the wiring system.
Features
The
following
paragraphs
describe
the
remote
annunciator specific features.
Alarm Horn
Alarm Horn.
The alarm horn sounds when a fault or
prealarm condition exists, except emergency stop,
battery charger fault, or low battery voltage. Silence the
alarm horn when the generator set master switch is in
the AUTO position. The alarm horn will not silence when
the NOT IN AUTO lamp is lit.
See the installation
procedure, step 8, for the resetting instructions.
Surface-Mount Remote Annunciator
14-Relay Dry Contact Box
A-293983
A-258782
P
FBA--1
42B
10 AMP
NO
C
C
NO
C
NO
C
NO
C
NO
C
NO
C
NO
C
NO
C
NO
C
NO
C
NO
C
NO
C
NO
C
NO
K1
K2
K3
K4
K5
K6
K7
K8
K9
K10
K11
K12
K13
K14
INPUT
CONTACT RATINGS: 10A @120VAC RES. LOAD
.01A @28VDC MIN.
10A @28VDC MAX.
PCB ASSY A--320639
LOT NO.
42A
2
K1 K2
K3
K4
K5
K6
K7
K8
K9 K10 K11
K13 K14
K12
P
N
Figure 1
Remote Annunciator Alarm Panel