TP-6903 5/16a
Diagnostic Troubleshooting Codes 31
P-Code SPN FMI Description
Possible
Cause
Corrective
Action
P0642 3509
4 Sensor
Reference
Voltage A Circuit Low
Problem with 5 V
sensor power supply
circuit. Power supply
is less than 4.6 V.
Check electrical connection at
ECM for sensor power supply
circuit.
Check for sensor power supply
circuit shorts to ground.
Check for shorts by disconnecting
the TMAP and TP sensors.
Monitor the sensor power supply
while reconnecting the sensors
one at a time. If the voltage falls
when a sensor is added, replace
that sensor. Refer to
Section 5
.
P0643 3509
3 Sensor
Reference
Voltage A Circuit High
Problem with 5 V
sensor power supply
circuit. Power supply
is above 5.4 V.
Check electrical connection at
ECM for sensor power supply
circuit.
Check for a short circuit to battery
voltage or open circuit in sensor
ground wire.
Check for shorts by disconnecting
the TMAP and TP sensors.
Monitor the sensor power supply
while reconnecting the sensors
one at a time. If the voltage rises
when a sensor is added, replace
that sensor. Refer to
Section 5
.
P0646
876
4
A/C Clutch Relay
Control Circuit Low
Not applicable
Not applicable
P0647
876
3
A/C Clutch Relay
Control Circuit High
Not applicable
Not applicable
P0650 1213
31 Malfunction
Indicator
Lamp (MIL) Control
Circuit
Not applicable
Not applicable
P0652 3510
4 Sensor
Reference
Voltage B Circuit Low
Problem with 5 V
sensor power supply
circuit. Power supply
is less than 4.6 V.
Check electrical connection at
ECM for sensor power supply
circuit.
Check for sensor power supply
circuit shorts to ground.
Check for shorts by disconnecting
the TMAP and TP sensors.
Monitor the sensor power supply
while reconnecting the sensors
one at a time. If the voltage falls
when a sensor is added, replace
that sensor. Refer to
Section 5
.
P0653 3510
3 Sensor
Reference
Voltage B Circuit High
Problem with 5 V
sensor power supply
circuit. Power supply
is above 5.4 V.
Check electrical connection at
ECM for sensor power supply
circuit.
Check for a short circuit to battery
voltage or open circuit in sensor
ground wire.
Check for shorts by disconnecting
the TMAP and TP sensors.
Monitor the sensor power supply
while reconnecting the sensors
one at a time. If the voltage rises
when a sensor is added, replace
that sensor. Refer to
Section 5
.
P0654
836
31
Engine RPM Output
Circuit
Not applicable
Not applicable
P0655
623
31
Overheat Lamp Circuit
Not applicable
Not applicable
Summary of Contents for KG2204
Page 8: ...8 Safety Precautions and Instructions TP 6903 5 16a Notes ...
Page 44: ...44 Diagnostic Troubleshooting Codes TP 6903 5 16a Notes ...
Page 58: ...58 Fuel System Troubleshooting TP 6903 5 16a Notes ...
Page 100: ...100 TP 6903 Notes ...
Page 105: ...Notes ...
Page 106: ...Notes ...
Page 107: ......