22
TS_619_00 PW9000DPA S2 User Manual 13/3/17
3
Installation
3.1
Introduction
This chapter contains essential information concerning the unpacking, installation planning and cabling of the
PW9000DPA S2 UPS system.
3.2
Taking receipt of the UPS
The UPS and accessories are delivered on a purpose-designed pallet that is easy to move with a forklift or a pallet jack.
Depending on the method of shipping, the UPS is packed in a cardboard or wooden container designed to protect it from
mechanical and environmental damage. Further protection is provided by wrapping the equipment with a plastic sheet.
Before you accept the shipment ensure that the received package(s) correspond to the description shown in the delivery
documentation. Note that some ordered optional equipment packages might be shipped inside the UPS cabinet.
Carefully examine the packing container for signs of physical damage. The external 'Tip&Tel' (“FRAGILE” and “ARROW”)
indicators should be intact if the equipment has been transported in an upright position.
3.2.1 Reporting transportation damage
If the 'Tip&Tel' indicators are ruptured or there are other signs of suspected transportation damage you must inform the
carrier and Uninterruptible Power Supplies Ltd. immediately.
Other claims for shipping damage must be filed immediately when found, and the carrier must be informed of ALL claims
within seven days of receipt of the equipment. If the equipment is to be stored for longer than seven days before it is
installed, you should unpack it and inspect it for signs of internal damage before you put it into storage. Note that some
optional equipment packages might be shipped inside the UPS cabinet and these too should be checked for damage.
If the equipment is damaged you should store the packing materials for further investigation
Key Point:
If you are installing an external battery cabinet supplied by Uninterruptible Power Supplies Ltd. you
should refer to the manual that is provided with the cabinet for installation instructions.
WARNING:
All the operations described in this chapter must be supervised by suitably qualified personnel and
all aspects of the electrical installation must be carried out by an authorised electrician.
Uninterruptible Power Supplies Ltd. will take no responsibility for any personal injury or material damage
caused by incorrect cabling or operation, or activities which are not carried out in strict accordance with the
instructions contained in this manual.
WARNING:
Once the UPS equipment is installed it must be commissioned by an engineer approved by
Uninterruptible Power Supplies Ltd., or one of its service agents, before it is powered-up. Uninterruptible Power
Supplies Ltd. will take no responsibility for any personal injury or material damage caused by the application of
electrical power to this equipment before it has been fully commissioned.
CAUTION: Observe the following precautions when off-loading and moving the UPS:
•
Always keep the packages in an upright position.
•
Do not drop the equipment.
•
Do not stack the pallets.
WARNING:
If the Tip&Tell indicators indicate that the UPS has been tilted in transit DO NOT connect the
UPS to the mains electricity supply.