TS_619_00 PW9000DPA S2 User Manual 13/3/17
47
4: Operating Procedures
4.7
Operating in ‘on bypass’ mode
When operating the UPS system in ‘on bypass’ mode, the load is powered normally through the UPS bypass (‘on bypass’)
and switches to inverter (‘on inverter’) if the bypass supply fails.
4.7.1 How to Turn ON the UPS in ‘on bypass’ mode
1. Use the standard operating instructions in paragraph 4.3 but do not perform the ‘
Transfer the load to inverter:
’ stage
(step 15 onwards).
4.7.2 How to Turn OFF the UPS in ‘on bypass’ mode
1. Use the standard operating instructions in paragraph 4.5 beginning at step 5 – as the load is already operating on
bypass.
4.7.3 How to transfer between ‘on bypass’ and ‘on inverter’ mode
The UPS can be switched between the ‘on bypass’ and ‘on inverter’ mode through the module control panel load transfer
menu.
Transfer from ‘on inverter’ to ‘on bypass mode:
1. On the module control panel of any one UPS module:
a) Press the
UP
key once to access the menu system.
b) Use the
UP/DOWN
keys to move the cursor so that it is adjacent to
COMMANDS
then press the
ENTER
key.
c) Use the
UP/DOWN
keys move the cursor so that it is adjacent to
LOAD
TO
BYPASS
then press the
ENTER
key
d) All UPS modules will simultaneously transfer the load to the static bypass.
2. On all module control panel of every UPS module, verify that:
a) The
INVERTER
LED has extinguished.
b) The
BYPASS
LED is green.
c) The LCD displays
LOAD
NOT
PROTECTED
.
Transfer from ‘on bypass’ to ‘on inverter’ mode:
1. On the module control panel of any one UPS module:
a) Press the
UP
key once to access the menu system.
b) Use the
UP/DOWN
keys to move the cursor so that it is adjacent to
COMMANDS
then press the
ENTER
key.
c) Use the
UP/DOWN
keys move the cursor so that it is adjacent to
LOAD
TO
INVERTER
then press the
ENTER
key
d) The UPS module will transfer the load to the inverter.
2. On the module control panel of every UPS module, verify that:
a) The
BYPASS
LED is OFF.
b) The
INVERTER
LED is ON.
c) The LCD displays
LOAD
PROTECTED
.
CAUTION: When operating in the ‘on bypass’ mode there is a short supply break when the UPS switches to the
‘on-inverter’ mode, so this mode should be used only with a load that can withstand a brief supply break.
LINE 1
LINE 2
BY PASS
INVERTER
BATTERY
LOAD
LINE 1
LINE 2
BY PASS
INVERTER
BATTERY
LOAD