8: Specification
58
TS_619_00 PW9000DPA S2 User Manual 13/3/17
8.4
Output
8.5
Standards
Module Type
DPA 30
DPA 40
DPA 50
Output Rated Power per Module
kVA
30
40
50
1)
Output Rated Power per Module
KW
24
32
40
Output Current In @ cos
1.0 (400 V)
A
35
46.5
58
Output Rated Voltage
V
3x380/220V or 3x400/230V or 3x415/240V
Output Voltage Stability
%
Static: < ± 1%
Dynamic (Step load 0%-100% or 100%-0%) < ±4%
Output Voltage Distortion
%
With Linear Load < ±2%
With Non-linear Load (EN62040-3:2001) < ±4%
Output Frequency
Hz
50 Hz or 60 Hz
Output Frequency Tolerance
%
Synchronized with mains < ±2% or < ±4% (selectable)
Free running ±0.1%
Bypass operation
At Nominal Input voltage of 3x400 V ±15% or
190 V to 264 V ph-N
Permissible Unbalanced Load
(All 3 phases regulated independently)
%
100%
Phase Angle Tolerance
(With 100 % Unbalanced load)
Deg.
±0 deg.
Overload Capability on Inverter
%
125% load 10 min. 150% load 60 sec.
Output short capability (RMS)
A
Inverter: 2.2 to 2.4x In for 40 ms
Bypass: 10 x In for 10 ms
Crest - Factor (load supported)
3:1
1)
The bypass rated current is 63A with the following overload capabilities: 110% continuously, 125% for 60 minutes and 150% for 30
minutes.
Module Type
DPA 30
DPA 40
DPA 50
Safety
Product Standards: IEC/EN 62040-1
Standards: IEC/EN 60950-1
Electromagnetic Compatibility
Product standards: IEC/EN 62040-2
Standards: IEC/EN 61000-6-2, IEC/EN 61000-6-4,
IEC/EN 61000-4-2, IEC/EN 61000-4-3,
IEC/EN 61000-4-4, IEC/EN 61000-4-5,
IEC/EN 61000-4-6,
Emission Class
C3
Immunity Class
C3
Performance
IEC/EN 62040-3
Product Certification
CE
Degree of Protection
IP 20