32
TS_622_02 PowerWAVE 9500DPA User Manual User Manual 26/2/19
4
Installation
4.1
Introduction
This chapter contains essential information concerning the safe unpacking, positioning, installing and cabling of the
PowerWAVE 9500DPA UPS system.
4.2
Taking receipt of the UPS
The UPS and accessories are delivered on a purpose-designed pallet that is easy to move with a forklift or a pallet jack.
Depending on the method of shipping, the UPS is packed in a cardboard or wooden container designed to protect it from
mechanical and environmental damage. Further protection is provided by wrapping the equipment with a plastic sheet.
Before you accept the shipment ensure that the received package(s) correspond to the description shown in the delivery
documentation. Note that some ordered optional equipment packages might be shipped inside the UPS cabinet.
Carefully examine the packing container for signs of physical damage. The external 'Tip&Tel' (“FRAGILE” and “ARROW”)
indicators should be intact if the equipment has been transported in an upright position.
4.2.1 Reporting transportation damage
If the 'Tip&Tel' indicators are ruptured or there are other signs of suspected transportation damage you must inform the
carrier and Kohler Uninterruptible Power Ltd. immediately.
Other claims for shipping damage must be filed immediately when found, and the carrier must be informed of ALL claims
within seven days of receipt of the equipment. If the equipment is to be stored for longer than seven days before it is
installed, you should unpack it and inspect it for signs of internal damage before you put it into storage. Note that some
optional equipment packages might be shipped inside the UPS cabinet and these too should be checked for damage.
If the equipment is damaged you should store the packing materials for further investigation
Key Point:
If you are installing an external battery cabinet supplied by Kohler Uninterruptible Power Ltd. you
should refer to the manual that is provided with the cabinet for installation instructions.
WARNING:
All cabling operations must be supervised by an authorised electrician or other suitably
qualified person. All installation procedures must be carried out in strict accordance with the instructions
contained in this manual. Kohler Uninterruptible Power Ltd. will take no responsibility for any personal injury
or material damage caused by the incorrect installation, cabling or operation of this product.
WARNING:
Once the UPS equipment is installed it must be commissioned by an engineer approved by
Kohler Uninterruptible Power Ltd.
before it is powered-up
. Kohler Uninterruptible Power Ltd. will take no
responsibility for any personal injury or material damage caused by the application of electrical power to this
equipment before it has been fully commissioned.
CAUTION:
Observe the following precautions when off-loading and moving the UPS:
• Always keep the packages in an upright position.
• Do not drop the equipment.
• Do not stack the pallets.
WARNING:
If the Tip&Tell indicators indicate that the UPS has been tilted in transit DO NOT connect the
UPS to the mains electricity supply.