4.6.7 Module customer interface facilities
Each UPS cabinet is fitted with a customer interface board which enables various external monitoring and control
applications to be connected to the system to satisfy particular site requirements.
Details of the interface facilities and available options are provided in Chapter 9.
Figure 4.16 UPS Customer interface board connectors
Key Point:
All used options should be installed and connected prior to commissioning the UPS so that they can
be functionally checked as part of the commissioning procedure.
1
2
3
4
6
8
9
10
11
12
13
5
7
1
MODEM Slot for optional Modem/Ethernet card ONLY.
2
SNMP
Slot for optional SNMP card ONLY.
3
JD1
Sub D9 female connector
RS232 User interface – UPS system to computer.
4
USB
Standard USB interface – UPS system to computer.
5
LEDs
2 LEDs that indicate the interface board status.
6
JR3
RJ45 Port
RS485 communication for remote panel.
7
DIP SW
Module selection used by multidrop configuration.
8
JR2
RJ45 Port
RS485 communication for multidrop cable connected
between all the UPS cabinets. Used with RJ45 splitter
adapter to enable module daisy chaining.
9
X3
Terminal block used for external customer inputs.
10
X2
Terminal block with volt-free outputs for use with customer
remote indications panel.
11
X1
Castell interlock function.
12
SW1-9
9-pole configuration DIP switch used to configure module for
parallel operation.
13
JD8
Parallel communication bus connector. Used in parallel
cabinet system only, and fitted with parallel adapter board to
enable module daisy chaining.