52
TS_622_02 PowerWAVE 9500DPA User Manual 26/2/19
Power-up the load:
1. Connect the UPS system input supply.
a) Power will be applied to the UPS modules, but they will be turned OFF.
2. On every module control panel, verify that:
a) The
LINE
1
LED is green.
b) The
BATTERY
LED is flashing red.
c) All other mimic LEDs are OFF
d) The LCD displays
LOAD
OFF, SUPPLY
FAILURE
.
If necessary press the
RESET
button to obtain this display.
3. Close the external UPS system output isolation device.
4. Close the UPS maintenance bypass switch.
5. Turn on the load equipment.
a) The load is now powered through the maintenance bypass.
b) The module control panel mimic indications do not change.
c) The LCD displays
MANUAL
BYP
IS
CLOSED
.
6. Press the
RESET
button.
a) The LCD displays
LOAD
OFF, SUPPLY
FAILURE
.
Start the UPS module(s):
7. Carry out steps 8 to 14 on each UPS module in turn.
8. Close the bypass fuse (F2).
9. On the module control panel, simultaneously press both
ON/OFF
buttons.
The UPS module will begin to power up over approximately 60s.
10. On the module control panel, after 60s verify that:
a) The
LINE
2
LED is green (red during initial start-up).
b) The
BYPASS
LED is green.
c) The
INVERTER
LED is red.
d) The
BATTERY
LED is flashing red.
e) The LCD displays
LOAD
NOT
PROTECTED.
11. Close the module’s battery fuse (F3) and the external battery enclosure fuse.
12. On the module control panel, verify that:
a) The
BATTERY
LED flashes green then changes to a solid green within 5
minutes.
13. Close the parallel isolator switch (IA2).
14. On the module control panel, verify that:
a) The LCD displays
PARALLEL
SW CLOSED
.
15. Before you continue, ensure that the indications on the module control
panels of ALL modules are identical, and as described above.
Transfer the load to inverter:
16. If the
BYPASS
LED is green (on ALL modules), open the maintenance bypass switch.
Note: If the
BYPASS
LED is not green, repeat step 7 then seek trained advice if it still fails to light green.
17. Press the
Home
button on the display header bar.
a) The
HOME
screen should open.
18. Press the
Command
button of the
HOME
screen.
a) The
COMMAND
screen should open.
LINE 1
LINE 2
BY PASS
INVERTER
BATTERY
LOAD
LINE 1
LINE 2
BY PASS
INVERTER
BATTERY
LOAD
LINE 1
LINE 2
BY PASS
INVERTER
BATTERY
LOAD