UPS412-01-01 Kohler PW 5000/TP User Manual Dated 17-11-11
3-7
3: Installation
Figure 3.4 Kohler PW 5000/TP fuse & cable rating
Rectifier
Inverter
Static Switch
FA1
Fuse B
Load
DUAL INPUT FEED
Cable D
Cable B
Fuse C
Cable C
Rectifier
Inverter
Static Switch
Fuse A
Load
SINGLE INPUT FEED (standard)
Mains (3x380/220V,
3x400/230V,
3x415/240V)
Cable D
Cable A
EXTERNAL
BATTERY
CABINET
(option)
FA2
FA1
FA2
EXTERNAL
BATTERY
CABINET
(option)
FA3
(F1)
FA3
(F1)
Int. Batts.
Int. Batts.
FA4
FA4
Output
Switch
Maint.
Bypass
IA2
IA1
Maint.
Bypass
IA2
IA1
Output
Switch
SINGLE INPUT FEED
DUAL INPUT FEED
Notes:
1.
Fuse
and Cable recommendations to IEC 60950-1:2001
2.
The fuse and cable rating details in the above tables are a recommendation only.
3.
The UPS must be installed to prescribed IEC or local regulations.
4.
External DC Cables and Battery fuses are bespoke to the installation.
Power (kVA)
Fuse A (Agl/CB) (A)
Cable A (mm²)
Cable D (mm²)
10
3 x 20
5 x 2.5
5 x 2.5
15
3 x 32
5 x 4.0
5 x 4.0
20
3 x 40
5 x 6.0
5 x 6.0
25
3 x 40
5 x 6.0
5 x 6.0
30
3 x 63
5 x 10
5 x 10
40
3 x 80
5 x 25
5 x 25
50
3 x 80
5 x 25
5 x 25
Power (kVA)
Fuse B
(Agl/CB) (A)
Cable B (mm²)
Fuse C
(Agl/CB) (A)
Cable C (mm²)
Cable D (mm²)
10
3 x 20
5 x 2.5
3 x 20
5 x 2.5
5 x 2.5
15
3 x 32
5 x 4.0
3 x 32
5 x 4.0
5 x 4.0
20
3 x 40
5 x 6.0
3 x 40
5 x 6.0
5 x 6.0
25
3 x 40
5 x 6.0
3 x 40
5 x 6.0
5 x 6.0
30
3 x 63
5 x 10
3 x 63
5 x 10
5 x 10
40
3 x 80
5 x 25
3 x 80
5 x 25
5 x 25
50
3 x 80
5 x 25
3 x 80
5 x 25
5 x 25
Summary of Contents for PW 5000/TP
Page 1: ...Pioneering solutions for total power protection Kohler PW 5000 TP User Manual ...
Page 2: ......
Page 8: ...IV UPS412 01 01 Kohler PW 5000 TP User Manual Dated 17 11 11 ...
Page 10: ...1 Safety 1 2 UPS412 01 01 Kohler PW 5000 TP User Manual Dated 17 11 11 ...
Page 66: ...7 Options 7 8 UPS412 01 01 Kohler PW 5000 TP User Manual Dated 17 11 11 ...
Page 72: ...8 Specifications 8 6 UPS412 01 01 Kohler PW 5000 TP User Manual Dated 17 11 11 ...