3: Installation
3-8
UPS412-01-01 Kohler PW 5000/TP User Manual Dated 17-11-11
Cabling a parallel system
In order to achieve equal load sharing between the UPS-cabinets in a multi-cabinet installation, the input
cables from the input distribution board to each UPS cabinet should be of equal length. Similarly the UPS
output cables to the output distribution board should be of equal length
(See Figure 3.5)
.
Figure 3.5 Cable lengths for multi cabinet configurations (assuming a dual input supply)
UPS 1
UPS 2
UPS 3
UPS 4
UPS 1
UPS 2
UPS 3
UPS 4
Recommended cable configurations
The cable configuration below is not recommended
Bypass Feed
Rectifier Feed
To Load
To Load
Bypass Feed
Rectifier Feed