UPS412-01-01 Kohler PW 5000/TP User Manual Dated 17-11-11
3-13
3: Installation
3.6
Connecting the UPS input supply
3.6.1 Safety
notes
Please ensure you read and understand the following safety notes before you begin the UPS electrical
installation.
1.
All operations detailed in this section must be performed by an authorised electrician or qualified
personnel.
2.
Once the electrical installation is completed the initial UPS start-up must be performed by qualified
personnel authorised by the manufacturer.
3.
Do not operate the UPS if there is water or moisture present.
4.
When carrying out any work on the UPS input power cables you must ensure that the UPS supplies are
isolated at the supply distribution panel and, where possible, locked out. Warning notices should be
posted where applicable to prevent inadvertent operation of the input supply isolators.
3.6.2 Preparation for the input cabling
Before you start connecting the UPS input cables:
• Ensure that the provided fuses and cables satisfy the ratings shown in Figures 3.4 and 3.6/ 3.7, and
are in accordance with the prescribed IEC Standards or local regulations.
• Do not commence this procedure until the UPS is properly installed at its intended location.
3.6.3 Connecting the UPS input power cables
1.
To protect personnel during the UPS installation ensure that the connections are performed under the
following conditions:
a)
No mains voltage is present.
b)
Loads are shut down and disconnected.
c)
The UPS is shut down and voltage-free.
d)
The UPS Maintenance Bypass Isolator IA1 is OFF.
e)
The UPS Output/Parallel Isolator IA2 is OFF
2.
Gain access to the UPS power terminals.
3.
Connect the earth cable from the LV-Distribution Board to the protective earth (PE) busbar in the UPS,
located adjacent to the power terminals, as shown in Figures 3.10, 3.11, 3.12.
4.
The Kohler PW 5000/TP input supply can be wired for ‘single feed’ (standard) or ‘dual feed’ operation.
Connect the input power cable coming from the LV-Distribution Board to the UPS input terminals
following the ‘single input feed’ or ‘dual input feed’ given below.
Single Input Feed
1.
Refer to the schematic drawing and connection table in Figure 3.8. Connect the UPS input supply cables
to terminals 1L1, 1L2, 1L3 and 1N on the UPS main terminal block
(See Figures 3.6 /3.7)
. Ensure correct
(clockwise) phase rotation.
2.
Secure the cables to the fixing rail under the connection terminals.
3.
10kVA – 25kVA Models only: Ensure the bypass cables are connected to the correct terminals on the
Filter Board (see Figure 3.6). These will be reconfigured by the commissioning engineer if necessary.
WARNING:
Opening or removing the UPS-covers will create the risk of exposure to
dangerous voltages if power is connected to the UPS.
CAUTION: The input Neutral cable must ALWAYS be connected.
Summary of Contents for PW 5000/TP
Page 1: ...Pioneering solutions for total power protection Kohler PW 5000 TP User Manual ...
Page 2: ......
Page 8: ...IV UPS412 01 01 Kohler PW 5000 TP User Manual Dated 17 11 11 ...
Page 10: ...1 Safety 1 2 UPS412 01 01 Kohler PW 5000 TP User Manual Dated 17 11 11 ...
Page 66: ...7 Options 7 8 UPS412 01 01 Kohler PW 5000 TP User Manual Dated 17 11 11 ...
Page 72: ...8 Specifications 8 6 UPS412 01 01 Kohler PW 5000 TP User Manual Dated 17 11 11 ...