8: Specifications
8-2
UPS412-01-01 Kohler PW 5000/TP User Manual Dated 17-11-11
8.2
Input Characteristics
8.3
Output Characteristics
Module Rating (kVA)
10
15
20
25
30
40
50
Nominal Input Voltage
V
3x380/220V+N, 3x400V/230V+N, 3x415/240V+N
Input Voltage Tolerance
(ref to 3x400/230V) for Loads in %:
V
(-23%/+15%) 3x308/177 V to 3x460/264 V for <100% load
(-30%/+15%) 3x280/161 V to 3x460/264 V for < 80% load
(-40%/+15%) 3x240/138 V to 3x460/264 V for < 60% load
Input Frequency
Hz
35 - 70
Input Power Factor
PF=0.99 @ 100% load
Inrush Current
A
max. In
Input Distortion THDi
Sine-wave THDi = 3.0% @ 100% load
Max. Input Power with rated output power and charged
battery (output pf = 0.9)
kW
9.6
14.4
19.1
23.9
28.7
38.3
47.9
Max. Input Current with rated output power and charged
battery (output pf = 0.9)
A
13.9
20.8
27.8
34.7
41.6
55.5
69.4
Max. Input Power with rated output power and discharged
battery (output pf = 0.9)
kW
10.5
15.7
21
26.2
31.4
41.9
52.4
Max. Input Current with rated output power and
discharged battery (output pf = 0.9)
A
15.2
22.8
30.4
37.9
45.5
60.7
75.9
Module Rating (kVA)
10
15
20
25
30
40
50
Output Rated Power
KW
9
13.5
18
22.5
27
36
45
Output Current In @ p.f. 0.9 (400 V)
A
13.0
19.5
26.0
32.5
39.0
52.0
65.0
Output Current In @ p.f. 1.0 (400 V)
A
14.4
21.7
28.9
36.1
43.3
57.7
72.2
Output Rated Voltage
V
3x380/220V or 3x400/230V or 3x415/240V
Output Voltage Stability
%
Static: < ±1%
Dynamic (Step load 0%-100% or 100%-0%) < ±4%
Output Voltage Distortion
%
With Linear Load < 2%
With Non-linear Load (EN62040-3:2001) < 4%
Output Frequency
Hz
50 Hz or 60 Hz
Output Frequency Tolerance
%
Synchronized with mains < ±2%
(selectable for bypass operation) or < ±4%Free running ±0.1%
Bypass operation
At Nominal Input voltage of 3x400 V ±15%, or 196 V to 264 V ph-N
Permissible Unbalanced Load
(All 3 phases regulated independently)
%
100%
Phase Angle Tolerance
(With 100% Unbalanced load)
Deg.
±0 deg.
Overload Capability on Inverter
%
At p.f. 0.9 110% load 10 min.
At p.f. 0.9 130% load 1 min.
At p.f. 0.8 125% load 10 min.
At p.f. 0.8 150% load 1 min.
Output short capability (RMS)
A
Inverter:up to 3 x In during 40 ms
Bypass: 10 x In during 10 ms
Crest - Factor
3: 1
Summary of Contents for PW 5000/TP
Page 1: ...Pioneering solutions for total power protection Kohler PW 5000 TP User Manual ...
Page 2: ......
Page 8: ...IV UPS412 01 01 Kohler PW 5000 TP User Manual Dated 17 11 11 ...
Page 10: ...1 Safety 1 2 UPS412 01 01 Kohler PW 5000 TP User Manual Dated 17 11 11 ...
Page 66: ...7 Options 7 8 UPS412 01 01 Kohler PW 5000 TP User Manual Dated 17 11 11 ...
Page 72: ...8 Specifications 8 6 UPS412 01 01 Kohler PW 5000 TP User Manual Dated 17 11 11 ...