3: Installation
3-2
UPS306-01-00 PowerWAVE 9000 DPA User Manual Dated 01-06-2010
3.3
Unpacking
If the packages are received in good order (i.e. the ‘tip & tell’ “FRAGILE” and “ARROW” indications on the
packing container are intact) then perform the following steps to unpack the UPS:
1.
If the cabinet is shipped inside a wooden case, remove the screws at the base and sides of the case then
carefully remove the case from the equipment.
2.
Cut the wrappers and remove the packing container by pulling it upwards.
3.
Remove the plastic sheeting covering the UPS.
4.
Remove the UPS from the pallet.
5.
Retain the packaging materials for future shipment of the UPS.
6.
Examine the UPS for any sign of damage.
Notify your supplier immediately if damage is apparent.
7.
Open the cabinet door and ensure that all the UPS modules are correctly and securely fitted in their
compartments. Ensure that a protection cover is fitted to the front of any empty UPS compartments.
3.3.1 Nameplate
The technical specifications of the PowerWAVE 9000 DPA are provided on the nameplate which is situated
at the front (internal door) of the UPS.
Check that the details on the nameplate corresponds to the purchased material detailed on the delivery note.
3.4
Batteries
The standard batteries connected to the UPS are sealed, maintenance-free batteries which will be mounted
either within the UPS cabinet or an external battery cabinet. The battery will usually be connected when the
UPS is commissioned.
Battery life depends very much on the ambient temperature, and optimum battery life will be obtained if the
batteries are operated at a temperature of 20°C.
If the UPS is delivered without batteries, Kohler Uninterruptible Power is not responsible for any damage or
malfunctioning caused to the UPS by the incorrect storage, installation or connection of batteries by third
parties.
CAUTION: Storage:
– The UPS should be stored in the original packing and shipping carton.
– The recommended storing temperature for the UPS system and batteries is b5 °C
and +40°C.
– The UPS system and the battery sets must be protected from humidity
< 90% RF (non-condensing).
WARNING:
The UPS system, the battery cabinet (option) and the batteries are heavy and
may tip during transportation causing serious injury if the unpacking instructions are not
followed closely.
Summary of Contents for PW 9000DPA
Page 1: ...User Manual Pioneering solutions for total power protection Kohler PW 9000DPA ...
Page 2: ......
Page 8: ...iv UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Page 10: ...1 Safety 1 2 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Page 18: ...2 Description 2 8 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Page 76: ...7 Options 7 6 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Page 85: ...UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 8 9 8 Specifications ...
Page 86: ...8 Specifications 8 10 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...