UPS306-01-00 PowerWAVE 9000 DPA User Manual Dated 01-06-2010
3-3
3: Installation
3.5
Storage
3.5.1 UPS
If you plan to store the UPS prior to use, store it in a clean dry environment with a temperature between 5°C
to +40°C and RH of less than 90%. If the packing container is removed, you must protect the UPS from dust.
3.5.2 Battery
The UPS utilizes sealed, maintenance-free batteries, whose storage capability depends on ambient
temperature. It is therefore important not to store the UPS for longer than 6 months at 20°C, 3 months at
30°C or 2 months at 35°C storage temperature without recharging the batteries. For longer term storage the
battery should be fully recharged every 6 months @20°C.
3.6
Positioning
3.6.1 Planning the installation
A certain amount of pre-planning will help ensure smooth, trouble-free equipment installation. The following
guidelines should be taken into account when planning a suitable UPS location and environment.
1.
The equipment must be installed and transported in a upright position.
2.
The floor at the installed location and en-route from the off-loading point must be able to safely take the
weight of the UPS and battery equipment plus fork lift during transit.
3.
The UPS cabinet requires space to bottom/front and back to enable cooling airflow. Suitable ventilation
airflow must also be provided
(See Figure 3.1)
. Allow a 200mm minimum clearance at the back of the
cabinet.
4.
All parts of the UPS required for maintenance, servicing and user operation are accessible from the front.
Reserve a minimum of 1000mm space at the front of the UPS cabinet.
5.
An ambient temperature of 20°C is recommended to achieve a long battery life. The cooling air entering
the UPS must not 40°C.
6.
Avoid high ambient temperature, moisture and humidity. The floor material should be non-flammable and
strong enough to support the heavy load.
7.
In summary, the UPS should be located where:
a)
Humidity (< 90% non-condensing) and temperature (+15°C to 25°C) are within prescribed limits.
b)
Fire protection standards are respected.
c)
Cabling can be performed easily.
d)
A minimum 900mm front accessibility is available for service or periodic maintenance.
e)
Requested air cooling flow is available.
f)
The air conditioning system can provide a sufficient amount of air cooling to keep the room at, or
below, the maximum desired temperature.
g)
No dust or corrosive/explosive gases are present.
h)
The location is vibration free.
i)
If the UPS will be installed in bayed enclosures, partition walls have to be installed.
CAUTION: Sealed batteries must never be stored in a discharged or partially discharged state.
Extreme temperature, under-charge, overcharge or over-discharge will destroy batteries!
Key Point:
Note the following:
•
Charge the battery both before and after storing.
•
Always store the batteries in a dry, clean, cool environment in their original packaging.
•
If the packaging is removed protect the batteries from dust and humidity.
Summary of Contents for PW 9000DPA
Page 1: ...User Manual Pioneering solutions for total power protection Kohler PW 9000DPA ...
Page 2: ......
Page 8: ...iv UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Page 10: ...1 Safety 1 2 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Page 18: ...2 Description 2 8 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Page 76: ...7 Options 7 6 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Page 85: ...UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 8 9 8 Specifications ...
Page 86: ...8 Specifications 8 10 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...