3: Installation
3-4
UPS306-01-00 PowerWAVE 9000 DPA User Manual Dated 01-06-2010
Figure 3.1 UPS & Battery Cabinet Space Requirements
3.7
UPS Power Cabling (preparation and planning)
3.7.1 General
requirements
It is the customer’s responsibility to provide all external fuses, isolators and cables used to connect the UPS
input and output power supplies. The information in this section should assist in the planning and preparation
of the UPS power cabling.
The UPS input supply and bypass supply should be connected to the utility mains through a LV-Distribution
board and protected by a circuit breaker or fuse. This provides overload protection and also a means of
isolating the UPS from the mains supply when required. Similarly, the UPS output supply should be
connected to the load equipment via a suitably fused output distribution panel.
The UPS can be wired with a ‘single feed’ input (standard), whereby the UPS input supply is connected
internally to the UPS bypass circuit
(see Figure 3.5)
; or it can be wired with a ‘dual feed’ input, whereby the
UPS bypass circuit is connected to a dedicated ‘bypass’ supply
(see Figure 3.6)
. These diagrams identify the
UPS input/output cabling requirements and provides information regarding fuse ratings, cable ratings and
cable sizing.
Figure 3.4 outlines of the power terminal connections withing the various UPS cabinets including connection
sizes. Detailed connection diagrams can be found in:
• Figure 3.7
(DPA-25 Input/Output Terminal Block, Front View)
• Figure 3.8
(DPA-75 Input/Output Terminal Block, Front View)
• Figure 3.9
(DPA-125 Input/Output Terminal Block, Front View)
• Figure 3.10
(DPA-50 Input/Output Terminal Block, Front View)
• Figure 3.11
(DPA-150 Input/Output Terminal Block, Front View)
• Figure 3.12
(DPA-250 Input/Output Terminal Block, Front View)
Key Point:
This information is given for guidance only. All fuses, isolators and power cables must
be rated and installed in accordance with the prescribed IEC standards or local regulation.
UPS
UPS
Battery
Cabinet
X
X
Y
Y
Z
Z
Front
Front
Clearance (mm)
X
Y
Z
Minimum
200*
200
1000
*Rear access is essential for maintenance.
Summary of Contents for PW 9000DPA
Page 1: ...User Manual Pioneering solutions for total power protection Kohler PW 9000DPA ...
Page 2: ......
Page 8: ...iv UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Page 10: ...1 Safety 1 2 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Page 18: ...2 Description 2 8 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Page 76: ...7 Options 7 6 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Page 85: ...UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 8 9 8 Specifications ...
Page 86: ...8 Specifications 8 10 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...