8: Specifications
8-4
UPS306-01-00 PowerWAVE 9000 DPA User Manual Dated 01-06-2010
8.4
Output
Module Range
MD
MX
Module Type
DPA 10 DPA 15
DPA 20 DPA 25 DPA 30
DPA 40 DPA 50
Output Rated Power per Module
kVA
10
15
20
25
30
40
45 1)
Output Rated Power per Module
KW
8
12
16
20
24
32
40
Output Current In @ cos
Φ
1.0 (400 V)
A 11.6 17.4 23.2 29 35 46.5 58
Output Rated Voltage
V
3x380/220V or 3x400/230V or 3x415/240V
Output Voltage Stability
%
Static: < +/- 1% Dynamic
(Step load 0%-100% or 100%-0%) < +/- 4%
Output Voltage Distortion
%
With Linear Load < +/- 2% With Non-linear Load
(EN62040-3:2001) < +/- 4%
Output Frequency
Hz
50 Hz or 60 Hz
Output Frequency Tolerance
%
Synchronized with mains < +/- 2 % (selectable) or
< +/- 4 % Free r/- 0.1 %
Bypass operation
At Nominal Input voltage of 3x400 V +/- 15 % or
190 V to 264 V ph-N
Permissible Unbalanced Load
(All 3 phases regulated independently)
% 100%
Phase Angle Tolerance
(With 100 % Unbalanced load)
Deg.
+/- 0 deg.
Overload Capability on Inverter
%
125 % load 10 min. 150 % load 60 sec.
Output short capability (RMS)
A
Inverter: 2 x In during 250 ms
Bypass: 10 x In during 10 ms
Crest - Factor
3 : 1
1) On Inverter mode 50 KVA/40kW on Bypass mode 45 KVA/40kW
Summary of Contents for PW 9000DPA
Page 1: ...User Manual Pioneering solutions for total power protection Kohler PW 9000DPA ...
Page 2: ......
Page 8: ...iv UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Page 10: ...1 Safety 1 2 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Page 18: ...2 Description 2 8 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Page 76: ...7 Options 7 6 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Page 85: ...UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 8 9 8 Specifications ...
Page 86: ...8 Specifications 8 10 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...