3: Installation
3.2.1 Clearances
Figure 3.1 Tower installation clearances
Figure 3.1 shows the required clearances when planning a PW1000 tower installation. The total width of the system
hardware can range from 88mm, for a stand-alone UPS cabinet, up to 352mm where the maximum of three (optional)
battery cabinets are attached to the UPS cabinet – only one battery cabinet shown in the diagram above.
The left hand diagrams show the ‘operating’ clearances necessary to provide adequate cooling. For maintenance, at least
800mm side access is required, and where necessary the cables connected to the UPS should be made sufficiently long
to allow the UPS to manoeuvred to a position where the clearances shown in the right hand diagrams are obtainable.
Y Z
A
Front
A1
B1
1400mm
1000mm
Min. Clearance
For Maintenance
A
B
C
TOP
200mm
200mm
800mm
400mm
Min. Clearance
Normal Operation
A
B
C
TOP
200mm
200mm
800mm
400mm
Min. Clearance
Normal Operation
Y
B
B
B1
A1
Y
C
Y
Z
Z
Up to 3 battery cabinets can
be connected to the UPS
making maximum total
system width of 352mm
Y
Z
UPS Cabinet
88 x 405mm
Battery Cabinet
88 x 405mm
Notes
Up to 3 battery cabinets can
be connected to the UPS
making maximum total
system width of 352mm
Y
Z
UPS Cabinet
88 x 405mm
Battery Cabinet
88 x 405mm
Notes
A
Front
A
B
C
TOP
200mm
200mm
800mm
400mm
Min. Clearance
Normal Operation
A
B
C
TOP
200mm
200mm
800mm
400mm
Min. Clearance
Normal Operation
B
B
B1
A1
C
Up to 3 battery cabinets can
be connected to the UPS
making maximum total
system width of 352mm
Y
Z
UPS Cabinet
88 x 600mm
Battery Cabinet
88 x 600mm
Notes
Up to 3 battery cabinets can
be connected to the UPS
making maximum total
system width of 352mm
Y
Z
UPS Cabinet
88 x 600mm
Battery Cabinet
88 x 600mm
Notes
A1
B1
1600mm
1000mm
Min. Clearance
For Maintenance
A1
B1
1600mm
1000mm
Min. Clearance
For Maintenance
Z
PW1000 1kVA
(Tower Clearances)
PW1000 2kVA / 3kVA
(Tower Clearances)
Y Z
A
Front
A1
B1
1400mm
1000mm
Min. Clearance
For Maintenance
A
B
C
TOP
200mm
200mm
800mm
400mm
Min. Clearance
Normal Operation
Y
B
B
B1
A1
Y
C
Y
Z
Z
Up to 3 battery cabinets can
be connected to the UPS
making maximum total
system width of 352mm
Y
Z
UPS Cabinet
88 x 405mm
Battery Cabinet
88 x 405mm
Notes
A
Front
A
B
C
TOP
200mm
200mm
800mm
400mm
Min. Clearance
Normal Operation
B
B
B1
A1
C
Up to 3 battery cabinets can
be connected to the UPS
making maximum total
system width of 352mm
Y
Z
UPS Cabinet
88 x 600mm
Battery Cabinet
88 x 600mm
Notes
A1
B1
1600mm
1000mm
Min. Clearance
For Maintenance
Z
PW1000 1kVA
(Tower Clearances)
PW1000 2kVA / 3kVA
(Tower Clearances)