3: Installation
16
TS_600_00 PW1000 1-3kVA User Manual 6/4/17
Figure 3.2 Rack mounted installation clearances
When the UPS is rack-mounted a minimum of 200mm should be available between the rear of the UPS and the back of
the rack cabinet to enable adequate ventilation and provide space for cabling. It is permissible to install the PW1000 1kVA
model in a cabinet with a depth of 600mm, although this will only provide 195mm rear clearance rather than the desired
200mm shown in the above diagram.
The rack cabinet must have a ventilated door and a minimum clearance of 800mm must be provided at the front and rear
of the cabinet to allow full UPS access for installation and maintenance.
B
PW1000
1.0 kVA
(440x405mm)
600 mm
Rack
Front
A
B
PW1000
2.0 / 3.0 kVA
(440x600mm)
800 mm
Rack
Front
A
C1
C1
C1
C2
800mm
800mm
0mm
115°
A
B
C1
D
Min. Clearance
250mm
C2
D
D
It is necessary to open the door fully to fit/
remove the assembly. If the cabinet is
placed against a wall ensure sufficient
space is provided (C2).
The rack doors must be ventilated.
E
E
200mm
E