VERSO 50_v1.0.27_EN 33502027401_3_1 page 19/24
2- 7 M6 - EJPT setup
It permits to activate the remote start if the inputs J4.4 is closed to negative. In this case, after a “Start delay” time, the remote start
output is activated and, when the generator is within the limits, after “KG delay” the mains contactor is opened and the generator
contactor is closed.
When the input is open, if the mains is present the load is passed to the mains (opening of KG and closure of KR) then, after the
cooling time, the remote start output is removed.
If an alarm about the generator occurs, the management follows the programmation of parameter "E - No KR with EJPT":
a) If No KR with EJPT is set to Off: KG is opened and the load passes to the mains, with closure of KR. The remote start
output remains active (if the active alarm is not set for genset stopping).
b) If No KR with EJPT is set to On: KG is opened but the load is not passed to the mains. The remote start output remains
active (if the active alarm is not set for genset stopping).
POS.
NAME
DESCRIPTION
RANGE OF
VALUES
DEFAULT
SETTINGS
A
EJPT Enable
If ON the function is enabled, if OFF the function is disabled.
On/Off
On
B
Start delay
It is the delay time that elapses when the input J4.4 closes to
negative before the activation of the remote start output.
0-59 [min]
0
C
KG delay
It is the delay time that elapses after the starting of the generator
before the opening of KR and the closure of KG.
0-59 [min]
0
D
EJPT 2 input
Function disabled in the VERSO 50 with only 1 input.
On/Off
Off
E
No KR with EJPT
If ON, when EJPT mode is active (remote start input active), the
mains contactor opens and it’s not possible to close it also if the
generator is stopped by an alarm.
On/Off
Off
F
Off delay
It is the delay time during which the EJPT signal must be disabled to
permit the stopping of the generator and the switchin on the mains.
0-59 [s]
10
2- 8 M7 - Counters
POS.
NAME
DESCRIPTION
RANGE OF
VALUES
DEFAULT
SETTINGS
A
Run hours
Here you can set a value of the work hours, then confirm the
parameter D to set the actual work hours to this value.
0-999999 [h]
0
B
KG hours
Here you can set a value of the work hours with KG closed, then
confirm the parameter D to set the actual work hours with KG closed
to this value.
0-999999 [h]
0
C
KR hours
Here you can set a value of the hours with KR closed, then confirm
the parameter D to set the actual hours with KR closed to this value.
0-999999 [h]
0
D
Counter reset
Confirm this parameter to set the values at parameters A, B and C.
OK
-
2- 9 M8 - Measures
The measures setup allows to adjust the measured values for genset and mains voltages. For each measure it’s possible to set an
offset with 0.1V.
POS.
NAME
RANGE OF VALUES
DEFAULT SETTINGS
A
Offset VRG
-100 +100 (V/10)
0
B
Offset VSG
-100 +100 (V/10)
0
C
Offset VTG
-100 +100 (V/10)
0
D
Offset VRM
-100 +100 (V/10)
0
E
Offset VSM
-100 +100 (V/10)
0
F
Offset VTM
-100 +100 (V/10)
0
“G”=Generator, “M”=Mains
Offset Adjusted value
Summary of Contents for VERSO50
Page 2: ......
Page 4: ...VERSO 50_v1 0 27_FR 33502027401_3_1 page 1 24 ...
Page 25: ...3 2 Monophasé 100A VERSO 50_v1 0 27_FR doc 33502027401_3_1 Page 21 24 ...
Page 26: ...3 3 Triphasé 25A VERSO 50_v1 0 27_FR doc 33502027401_3_1 Page 22 24 ...
Page 27: ...VERSO 50_v1 0 27_FR doc 33502027401_3_1 Page 23 24 3 4 Triphasé 40A ...
Page 29: ...VERSO 50_v1 0 27_FR 33502027401_3_1 ...
Page 30: ...VERSO 50_v1 0 27_FR 33502027401_3_1 Distributeur agréé ...
Page 32: ...VERSO 50_v1 0 27_EN 33502027401_3_1 page 2 24 ...
Page 53: ...3 2 Single Phase 100A VERSO 50_v1 0 27_EN doc 33502027401_3_1 Page 21 24 ...
Page 54: ...3 3 Three Phase 25A VERSO 50_v1 0 27_EN doc 33502027401_3_1 Page 22 24 ...
Page 55: ...3 4 Three Phase 40A VERSO 50_v1 0 27_EN doc 33502027401_3_1 Page 23 24 ...
Page 57: ...VERSO 50_v1 0 27_EN 33502027401_3_1 ...
Page 58: ...VERSO 50_v1 0 27_EN 33502027401_3_1 Authorized distributor ...
Page 60: ...VERSO 50_v1 0 27_DE 33502027401_3_1 Seite 2 24 ...
Page 81: ...3 2 Eine Phase 100 A VERSO 50_v1 0 27_DE doc 33502027401_3_1 Seite 21 24 ...
Page 82: ...3 3 Drei Phasen 25 A VERSO 50_v1 0 27_DE doc 33502027401_3_1 Seite 22 24 ...
Page 83: ...3 4 Drei Phasen 40 A VERSO 50_v1 0 27_DE doc 33502027401_3_1 Seite 23 24 ...
Page 85: ...VERSO 50_v1 0 27_DE 33502027401_3_1 ...
Page 86: ...VERSO 50_v1 0 27_DE 33502027401_3_1 Vertragshändler ...
Page 88: ...VERSO 50_v1 0 27_ES 33502027401_3_1 Página 1 24 ...
Page 109: ...VERSO 50_v1 0 27_ES doc 33502027401_3_1 Página 21 24 3 2 Monofásico 100A ...
Page 110: ...VERSO 50_v1 0 27_ES doc 33502027401_3_1 Página 22 24 3 3 Trifásico 25A ...
Page 111: ...VERSO 50_v1 0 27_ES doc 33502027401_3_1 Página 23 24 3 4 Trifásico 40A ...
Page 113: ...VERSO 50_v1 0 27_ES 33502027401_3_1 ...
Page 114: ...VERSO 50_v1 0 27_ES 33502027401_3_1 Distribuidor autorizado ...
Page 116: ...VERSO 50_v1 0 27_PT 33502027401_3_1 Página 1 24 ...
Page 137: ...3 2 Fase simples 100A VERSO 50_v1 0 27_PT doc 33502027401_3_1 Página 21 24 ...
Page 138: ...3 3 Três Fases 25A VERSO 50_v1 0 27_PT doc 33502027401_3_1 Página 22 24 ...
Page 139: ...3 4 Três Fases 40A VERSO 50_v1 0 27_PT doc 33502027401_3_1 Página 23 24 ...
Page 141: ...VERSO 50_v1 0 27_PT 33502027401_3_1 ...
Page 142: ...VERSO 50_v1 0 27_PT 33502027401_3_1 Distribuidor autorizado ...
Page 144: ...VERSO 50_v1 0 27_RU 33502027401_3_1 Стр 1 24 ...
Page 165: ...3 2 Одна фаза 100 A VERSO 50_v1 0 27_RU doc 33502027401_3_1 Стр 21 24 ...
Page 166: ...3 3 Три фазы 25 A VERSO 50_v1 0 27_RU doc 33502027401_3_1 Стр 22 24 ...
Page 167: ...VERSO 50_v1 0 27_RU doc 33502027401_3_1 Стр 23 24 3 4 Три фазы 40 A ...
Page 169: ...VERSO 50_v1 0 27_RU 33502027401_3_1 Стр 25 24 ...
Page 170: ...VERSO 50_v1 0 27_RU 33502027401_3_1 Стр 26 24 Авторизованный дистрибьютор ...