AKD2G-S Installation Manual, Safety 1 | 10 Safety Manual
10.1.4 Enclosure, wiring
Enclosure
Since the drive meets IP20, you must select an enclosure that permits safe operation of the
drive. The enclosure must at least meet IP54 .
Transport in accordance with IEC 61800-2
Transport only in the manufacturer’s original recyclable packaging.
Temperature
-25 to +70 °C, maximum rate of change 20 K/hour, class 2K3.
Relative Humidity
max. 95% at +40°C, no condensation, class 2K3.
Shock
NOTICE:
Avoid shocks while transporting. AKD2G modules are
tested for environmental class 2M1 of IEC 60721-3-2.
Storage in accordance with IEC 61800-2
Temperature
-25 to +55 °C, maximum rate of change 20 K/hour, class 1K4.
Relative Humidity
5 to 95% , no condensation, class 1K3.
Operation in accordance with IEC 61800-2
Environmental class
Environmental class 3K3
Temperature
Internal regen resistor used:
0 to +40 °C under rated conditions
+40 to +60 °C with current derating 3 % per Kelvin
Internal regen resistor not used:
0 to +50 °C under rated conditions
+50 to +60 °C with current derating 2 % per Kelvin
Relative Humidity
5 to 85%, no condensation, IEC 61800-2 class 3K3
Site altitude
Up to 1000 m above mean sea level (AMSL): no restriction
1,000 to 2,000 m AMSL: power derating 1.5%/100 m
Maximum altitude: 2000 m AMSL
Drive EMC immunity
Increased immunity according to EN 61800-5-2
Drive Pollution level
Pollution level 2 as per IEC 60664-1
Drive Vibration class
Class 3M1 according to IEC 61800-2
Drive Shock class
Class L according to IEC 61800-2
Drive protection class
IP20 according to IEC 60529
Enclosure
Minimum cabinet size (WxHxD): 406 x 406 x 254 mm
Enclosure protection
At least IP 54 according to IEC 60529
Wiring
Wiring inside the specified enclosure (IP54) must meet the requirements of the standard
IEC 60204-1 and ISO 13849-2 (Table D.4). Use copper wires, 0.5 mm² (20 awg), wire fer-
rules. Maximum distance for unshielded I/O lines is 3 m inside the cabinet. If the I/O cable
leaves the cabinet, it must be EMC shielded.
Wiring outside the specified enclosure must be laid durably protected from outside damage
(for example, by laying the cable in a duct, placed in different sheathed cables, or protected
individually by grounding connection).
When wiring the digital inputs and outputs, take care, that short circuits between the inputs,
the outputs or to a supply line are avoided.
136