6.5 Electrical data
6.5.1 Single axis variants (S)
6.5.1.1 Mains supply data, 1 phase AC, type AKD2G-Sxx- (S)
Input data
Units
6V03S
6V06S
6V12S
Operational supply voltage (line-line)
VAC
12 to 265
Rated supply voltage
VAC
240
Rated supply input frequency (±5%)
Hz
50 to 60
Permitted switch on/off frequency
1/h
30
Rated input VA at 240 V
kVA
1.0
1.7
3.1
Rated input current
A
4.0
7.1
13
Max. inrush current
A
10
Rated DC bus link voltage
VDC
300
6.5.1.2 Mains supply data, 3 phase AC, type AKD2G-Sxx- (S)
Input data
Units 6V03S
6V06S
6V12S
7V03S
7V06S
7V12S
Operational supply voltage (L1/L2/L3)
VAC
12 to 265
24 to 525
Rated supply voltage
VAC
240
480
Rated supply input frequency (±5%)
Hz
50 to 60
Permitted switch on/off frequency
1/h
30
Rated input VA at 240 V (* at 480 V)
kVA
1.3
2.2
4.0
2.7*
4.4*
7.2*
Rated input current
A
3.2
5.3
9.7
3.2
5.3
8.7
Max. inrush current
A
10
Rated DC bus link voltage
VDC
310
620
6.5.1.3 Mains supply data, DC, type AKD2G-Sxx- (S)
Input data
Units 6V03S
6V06S
6V12S
7V03S
7V06S
7V12S
Operational supply voltage (DC+/DC-)
VDC
17 to 370
34 to 740
Rated supply voltage
VDC
340
680
Permitted switch on/off frequency
1/h
30
Rated input power at 340 V (* at 680 V)
kW
0.62
1.25
2.5
1.25*
2.5*
5.0*
Rated input current
A
2.0
4.0
8.0
2.0
4.0
8.0
Max. inrush current through AC input
A
10
Rated DC bus link voltage
VDC
340
680
6.5.1.4
Auxiliary voltage input data, 24VDC, type AKD2G-Sxx- (S)
Input data
Units 6V03S
6V06S
6V12S
7V03S
7V06S
7V12S
Aux. voltage supply (PELV)
VDC
24 V (±10%, check voltage drop)
- control current without motor brake
A
< 1.0
- control current with one motor brake
A
< 3.1
AKD2G-S Installation Manual, Safety 1 | 6 Technical description and data
Kollmorgen | kdn.kollmorgen.com | July 2020