AKD2G-S Installation Manual, Safety 1 | 8 Electrical Installation
8.15.5.2 Digital-In 3 to 12
These inputs (IEC 61131-2 Type 1) are programmable with the setup software.
Manufacturer setting:
Digital-In 3: HW-Enable Axis 1
Digital-In 4: HW-Enable Axis 2
Digital-In 5 ...12: off
Choose the function you require in WorkBench. For more information refer to WorkBench.
Technical characteristics
Floating, reference common line is DGND
High: 11 to 30 V/2 to 15 mA , Low: -5 to +5 V/<15 mA
Update rate: firmware reads hardware input state every 250 µs
Wiring example
108
Kollmorgen | kdn.kollmorgen.com | July 2020