AKD2G-S Installation Manual, Safety 1 | 6 Technical description and data
6.5.2.5 Output data, type AKD2G-Sxx- (D)
Drive current and power output values are listed for Axis1/Axis2.
Units
6V03D
6V06D
7V03D
7V06D
Continuous output current ( ± 3%)
Arms
3/3
6/6
3/3
6/6
Peak output current (for 5s, ±3%)
Arms
9/9
18/18
9/9
18/18
Continuous motor shaft output power at rated input current
at 1 x 120 VAC
kW
0.22/0.22
0.44/0.44
-
-
at 1 x 240 VAC
kW
0.44/0.44
0.875/0.875
-
-
at 3 x 120 VAC
kW
0.31/0.31
0.625/0.625
-
-
at 3 x 240 VAC
kW
0.625/0.625
1.25/1.25
0.625/0.625
1.25/1.25
at 3 x 400 VAC
kW
-
-
1.05/1.05
2.1/2.1
at 3 x 480 VAC
kW
-
-
1.25/1.25
2.5/2.5
at 170 VDC
kW
0.31/0.31
0.625/0.625
-
-
at 340 VDC
kW
0.625/0.625
1.25/1.25
0.625/0.625
1.25/1.25
at 565 VDC
kW
-
-
1.05/1.05
2.1/2.1
at 680 VDC
kW
-
-
1.25/1.25
2.5/2.5
Peak output power (for 1 s)
at 1 x 120 VAC
kW
1.1/1.1
2.1/2.1
-
-
at 1 x 240 VAC
kW
2.1/2.1
4.2/4.2
-
-
at 3 x 120 VAC
kW
1.5/1.5
3.0/3.0
-
-
at 3 x 240 VAC
kW
3.0/3.0
6.0/6.0
3.0/3.0
6.0/6.0
at 3 x 400 VAC
kW
-
-
5.0/5.0
10/10
at 3 x 480 VAC
kW
-
-
6.0/6.0
12/12
at 170 VDC
kW
1.5/1.5
3.0/3.0
-
-
at 340 VDC
kW
3.0/3.0
6.0/6.0
3.0/3.0
6.0/6.0
at 565 VDC
kW
-
-
5.0/5.0
10/10
at 680 VDC
kW
-
-
6.0/6.0
12/12
Noise emission at 1 m,
low/high speed fan
dB(A)
< 50 / 60
Thermal dissipation, disabled
W
15
15
15
15
Thermal dissipation at rated current
W
90
150
120
210
Motor inductance
minimum at 120 VAC
mH
1.2/1.2
0.6/0.6
-
-
minimum at 240 VAC
mH
2.4/2.4
1.2/1.2
3.1/3.1
1.9/1.9
minimum at 400 VAC
mH
-
-
5.1/5.1
3.2/3.2
minimum at 480 VAC
mH
-
-
6.1/6.1
3.8/3.8
maximum
mH
240/240
120/120
610/610
380/380
Regeneration Braking
Brake output
Voltage (±10%)
VDC
24
Voltage power saving
VDC
12 to 24
Output under current fault
mA
100 (required for fault detection)
Output over current fault
A
2.25 (required for fault detection)
Output current, maximum
A
2.1 per brake
36
Kollmorgen | kdn.kollmorgen.com | July 2020