TESTING AND ADJUSTMENTS
WB97S-5
20-55
TESTING THE AIR-CONDITIONING UNIT
TESTING THE AIR-CONDITIONING UNIT
a
Test conditions:
•
Machine on level ground with the working
equipment raised and in safety conditions
•
Parking brake engaged
1. Testing the working temperature
1 -Connect the maintenance station to the high pressure
valve (H.P.) and the low pressure valve (L.P.)
2 -Start the engine and bring it up to a speed of 1500 rpm.
3 -Switch on the A/C unit using the switch in the cab.
4 -Select an intermediate ventilation speed inside the cab.
5 -Use the thermometer/hygrometer
M2
to check that the
temperature inside the cab is equal to or lower than the
ambient temperature.
a
If the temperature of the cab is higher than the
ambient temperature, open the doors and widows
and wait until the cab temperature stabilizes at the
outside value.
6 -Close the doors and windows and let the A/C unit
operate in these conditions for 5 - 10 minutes.
7 -Use the thermometer
M2
to check the temperature of
the air at the central outlets.
a
Position the probe as close as possible to the air
outlets.
8
-Compare the average value of the measured
temperatures using the following table:
9 -f the average value of the temperature measured does
not fall within the values given in the table, it will be
necessary to thoroughly check the unit.
Ambient
temperature (°C)
20
25
30
35
Outgoing
air temperature
(°C)
6
--
8
8
--
10
8
--
12
9
--
14
RKZ11010
Summary of Contents for WB97S-5
Page 1: ...WEBM007500 WB97S 5 BACKHOE LOADER SERIAL NUMBER F00003 and up WB97S 5 SHOP MANUAL ...
Page 2: ......
Page 4: ...PAGE INTENTIONALLY LEFT BLANK ...
Page 48: ...PAGE INTENTIONALLY LEFT BLANK ...
Page 50: ...PAGE INTENTIONALLY LEFT BLANK ...
Page 65: ...PAGE INTENTIONALLY LEFT BLANK ...
Page 144: ...PAGE INTENTIONALLY LEFT BLANK ...
Page 146: ......
Page 161: ...TESTING AND ADJUSTMENTS WB97S 5 20 17 NORMAL OR STANDARD TECHNICAL DATA Fig S RKZ10830 ...
Page 264: ...PAGE INTENTIONALLY LEFT BLANK ...
Page 400: ...PAGE INTENTIONALLY LEFT BLANK ...
Page 508: ...PAGE INTENTIONALLY LEFT BLANK ...
Page 566: ......
Page 581: ...40 15 WB97S 5 STANDARD MAINTENANCE CONTROL VALVE RKZ09071 C C B B A A AE AE X View X ...
Page 589: ...40 23 WB97S 5 STANDARD MAINTENANCE CONTROL VALVE ViewX RKZ09591 C C B B A A AE AE ...
Page 603: ...PAGE INTENTIONALLY LEFT BLANK ...
Page 610: ......
Page 611: ...90 1 WB97S 5 90 OTHER ELECTRICAL DIAGRAM STANDARD VERSION 3 ...
Page 612: ......
Page 614: ......
Page 615: ......
Page 616: ... 2006 KOMATSU UTILITY EUROPE S p A All Rights Reserved Printed in Europe 06 2006 ...