2.5.2.1. Air quality control

Air quality control is designed according to:

•  CO

2

 sensor [0...2000 ppm];

• 

air quality sensor VOCq [0...100 %];

• 

air pollution sensor VOCp [0...100 %];

• 

relative humidity sensor [0...100 %];

Depending on the type of the selected sensor, the value of the air quality 

function to be maintained is set, and the air handling unit intensity will be adjusted 

according to that value. Ventilation intensity will be increased automatically in the 

case of deviation from the set value and decreased again when it is approached. 

For example, if the unit is designed with the CO

2

 maintenance function and is 

equipped with a CO

2

 sensor, after setting value 800 ppm, this set CO

2

 level will 

be maintained by adjusting ventilation intensity, i.e. ventilation intensity will be 

increased if the CO

2

 level grows and will be decreased when it returns to the 

previous condition.

This function is provided only in units with EC fans.

2.5.2.2. Exhaust air flow correction 

Set air flow intensity (or maintained air volume) for 1–99 minutes period can be 

corrected from -50 % till +50 % from set value. Example, after reducing exhaust 

air flow intensity, for some time overpressure will be caused (sometimes needed 

to start the fireplace or such).

Note: After this function has been activated unit will work for the set time period 

with present exhaust correction. After time period is over this function turns off 

automatically.

This function is provided only in units with EC fans. This function is not 

available in supply air units (OTK).

2.5.2.3. Summer night cooling 

If the room temperature (exhaust air) in summertime is 5 °C higher than the set-

point and outside temperature is between 12 °C and the setpoint, the ventilation 

level is automatically switched to the third intensity level at 00:15 am. The unit 

will operate in the third intensity level until 06:00 am or when outside air cools 

down (warms up) too much or the room temperature equals the setpoint. The air 

is being cooled only by fans, without heat or coolness recovery and additional air 

heating or cooling. When function is switched off the unit continues operating in 

the previous mode.

Function starts operating automatically if only the unit operates in the 

first or second operation mode. Function stops operating, when the 

mode is being changed.

Summer night cooling and minimum temperature control functions can 

not be activated at the same time. When one is selected, another’s 

function operation is blocked.

Enable

Setpoint

1000 ppm

Sensor

CO

2

Air quality control

Enable

Extract flow

-50%

Time

1 min.

Exhaust air flow correction

Enable

Summer night cooling

Summary of Contents for C3.1

Page 1: ...EN Electrical installation and Operation Manual C3 1 ...

Page 2: ......

Page 3: ...me or your household waste disposal service Content 1 ELECTRICAL INSTALLATION MANUAL 4 1 1 Air Handling Units Sections Connection 4 1 2 Electric Power Supply Connection 4 1 3 External Elements Connection 5 1 4 Temperature Sensors Installation 8 1 5 Requirements for the installation of the control panel 8 1 6 Control panel connection 8 2 OPERATION MANUAL 9 2 1 Unit Control 9 2 2 Control panel indic...

Page 4: ...e is 230 V 50 Hz it is necessary to install the socket with grounding of correspond ing capacity see electric diagram unit If the voltage is 400 V 50 Hz the cable of electrical power supply is connected to the main switch which is located on the unit s outside wall It is necessary to connect earthing Types of cables of connection of electrical power supply are specified in 1 2 Table 1 2 Table Elec...

Page 5: ...n type B or B Before connecting unit to the electrical power supply it is necessary to check whether earthing has been installed properly 1 3 External Elements Connection In the air handling unit it is provided connection board 1 3 a picture or 1 3 b picture depending on the unit type all external elements are connected to connection board External elements connection diagram is given in the 1 3 c...

Page 6: ...rnal Elements Connection Diagram 1 3 c Picture 1 Used only in the units with water heater 2 Only in units with EC fans additional accessories required 3 In DOMEKT S VERSO S unit is not used 4 In units with AC fans is not used Control contact Do not connect voltage Normally closed contact Do not connect voltage ...

Page 7: ... Control System External Elements Connection Diagram 1 3 d Picture 1 Used only in the units with water heater 2 Only in units with EC fans additional accessories required 3 used only in VERSO P 7000 H units Normally closed contact Do not connect voltage Control contact Do not connect voltage ...

Page 8: ...wing conditions are ensured 1 1 ambient temperature 0 ºC 40 ºC 1 2 relative humidity range 20 80 1 3 protection against dripping of water IP X0 2 Control panel connection is provided through a hole in the back or bottom side 3 The panel can be mounted on a flush mounting box or in any other place just screwing two holes on the fastening surface Do not use any other type or size screws but those th...

Page 9: ...xtract room air quality Fan operation Energy recovery operation Air heater operation Air cooler operation Weekly operation mode Unit control activation by external contacts see Chapter 2 5 2 5 Alarm signal 2 OPERATION MANUAL 2 1 Unit Control Air handling units control system ensures control of the physical pro cesses that are taking place inside the air handling unit Control system consists of mai...

Page 10: ... OTK only supply air flow and temperature is indicated 2 4 Operation modes selection Three operation modes are possible one of them user can select directly from control panel main window MODE 1 2 3 for each of them the user can set air flow and temperature OFF mode completely turns off the unit Reset settings MODE 2 Supply air flow 1250 m3 h Extract air flow 1250 m3 h Setpoint 20 C MODE 1 21 9 C ...

Page 11: ... the notification of existing faults After failure elimination see chapter 2 8 messages are deleted by selecting Delete By clicking on History can be viewed up to 50 registered alarms 2 5 1 2 Detailed information All temperature sensor readings functioning of separate air handling unit ele ments and other detailed information is available in this menu Detailed information Supply air flow 350 m3 h ...

Page 12: ... will be caused sometimes needed to start the fireplace or such Note After this function has been activated unit will work for the set time period with present exhaust correction After time period is over this function turns off automatically This function is provided only in units with EC fans This function is not available in supply air units OTK 2 5 2 3 Summer night cooling If the room temperat...

Page 13: ...al signal short circuit on contacts 17 18 1 3 c Pic or 27 28 1 3 d Pic activates Override function and air handling unit starts to operate by the preset parameters If Override function is deactivated then mentioned contacts can be used for remote on off control of the unit see Chapter 2 6 1 Enable Min temperature control Enable Supply flow 1250 m3 h Extract flow 1250 m3 h Setpoint 20 C Override fu...

Page 14: ... flow in this case discharged air operates as the slave ventilation sys tem and always follows the master one If the supply air requirement in the ventilation system which is assigned as the master system decreases the intensity of discharged air in the slave system is reduced correspondingly by the same percentage If the variable air volume control function is mode is selected the initial calibra...

Page 15: ... Remote unit operation and failure indication If the information about unit operation mode is requested when unit is operating and when is not indication device for ex bulb must be connected to the contacts 33 35 see chapter 1 3 c Picture In the connection board see chapter 1 3 are provided contacts 33 34 see chapter 1 3 c Picture or 29 30 see chapter 1 3 d Picture which are intended for connectio...

Page 16: ...Electric heater overheating protection is on To restore protection it is possible only after pressing RESET button which is located on the heater Return water low temperature Return water temperature in water heater dropped lower allowable level Check circulation pump and heating system con dition heating valve actuator performance Frost possibility Temperature of the air passing through plate hea...

Page 17: ...perate and failure message is indicated 3 SAFETY REQUIREMENTS To avoid accidents and or unit damage only a trained technician must carry out the connection The appropriate Personal Protective Equipment PPE attire is worn relative to the operation being carried out Electrical equipment is rated connected and earthed in accordance with CE regulations Before performing any jobs inside the unit make s...

Page 18: ......

Page 19: ......

Page 20: ...ma www microclima hr HU AIRVENT Légtechnikai Zrt www airvent hu Gevent Magyarország Kft www gevent hu Merkapt www merkapt hu IR Fantech Ventilation Ltd www fantech ie IS Blikk Tækniþjónustan ehf www bogt is Hitataekni ehf www hitataekni is NL Ventilair group www ventilairgroup com DECIPOL Vortvent www vortvent nl NO Ventistål AS www ventistal no Thermo Control AS www thermocontrol no PL Ventia Sp ...

Reviews: