UAB KOMFOVENT we reserve the right to make changes without prior notice
13
C3.1-16-01
2.5.2.4. Minimum temperature control
In wintertime (outside temperature < 5°C), when heating power is not enough and
supply air temperature is 4°C below setting value, ventilation intensity automati-
cally is decreasing in one level. If there is not enough, one more level (up to mini-
mum) till set supply air temperature will be maintained.
Summer night cooling and minimum temperature control functions can
not be activated at the same time. When one is selected, another’s
function operation is blocked.
2.5.2.5. Override function
Unit is provided with remote control possibility using external device (button, timer,
other sensor) which is connected to the contacts 17, 18 (see chapter 1.3c Picture)
or 27, 28 (see chapter 1.3 d Picture). External signal (short-circuit on contacts 17-
18, 1.3 c Pic. or 27-28, 1.3 d. Pic.) activates “Override” function and air handling
unit starts to operate by the preset parameters.
If “Override” function is deactivated then mentioned contacts can be
used for remote on/off control of the unit (see Chapter 2.6.1.)
Enable
Min. temperature control
Enable
Supply flow
1250 m
3
/h
Extract flow
1250 m
3
/h
Setpoint
20 °C
Override funcion
2.5.3. Scheduling
Menu for planning of the air handling unit operation according to the weekly program. For each day of the week
there is a possibility to set up to 3 operation programs.
Functions
Settings
Overview
Scheduling
Meniu
Scheduling
Monday
Tuesday
Wednesday
Thursday
Friday
Enable
1 / 2
Monday
Operation mode
MODE 1
Start time
00:00
Stop time
00:00
Program 1
1 / 3
Note: Every program start and end time is set from 0:00 to 23:59 h.
2.5.4. Settings
This menu is for air handling unit and the user param-
eter setting.
Air handling unit
Personalization
Settings
Functions
Settings
Overview
Scheduling
Menu
Summary of Contents for C3.1
Page 1: ...EN Electrical installation and Operation Manual C3 1 ...
Page 2: ......
Page 18: ......
Page 19: ......