2.5.4.1. Air handling unit settings
Temperature control
The air handling unit provides for several temperature control modes:
• Supply
. The unit supplies air according to the temperature preset by the user.
• Extract
. Unit automatically supplies air of such temperature to maintain preset
exhaust air temperature.
• Auto.
When cooling is needed, unit will work in the extract air temperature
maintenance mode. If the outside temperature will be few degrees lower than
set value, control automatically will switch to supply air maintenance mode.
Note. This setting is not intended in supply air units (OTK).
Air volume control
Supply and exhaust air volumes control modes have been provided in the unit:
• CAV
– constant air volume control mode. The unit will supply and extract a constant air flow which is preset
by the user, irrespective of any changes occurring in the ventilation system;
• VAV
– variable air volume control mode. The unit will supply and extract an air flow with regard to the
ventilation needs in different rooms. In case of frequently changing ventilation demands this air volumes
maintenance mode signally reduces unit exploitation costs.
Menu window for air flow control is intended only in units with EC fans.
It is possible to use a simplified VAV control function, “single-flow VAV control”. It means that the perfor
-
mance of this function requires only a single air flow pressure sensor, which is installed in a variable air duct
system (e. g. in supply air). This variable system is called the master ventilation system, according to which
control is performed, while the other air flow (in this case, discharged air) operates as the slave ventilation sys
-
tem and always follows the master one. If the supply air requirement in the ventilation system which is assigned
as the master system decreases, the intensity of discharged air in the slave system is reduced correspondingly
by the same percentage.
If the variable air volume control function is mode is selected, the initial
calibration of the control mode must be performed; otherwise, the unit
will not operate if the VAV mode is selected.
Variable air volume control mode calibration:
1. Before start of calibration the air distribution and exhaust devices in ventilation system should be adjusted,
all valves for variable air flow in a way enabling air supply to all ventilated premises should be opened.
2. After switch on of the unit the VAV mode should be selected and calibration procedure should be confirmed.
After the end of the calibration, depending on the configuration of pressure sensors, VAV mode status will
change to Supply, Extract, Double.
3. After calibration the air handling unit further will operate in the previous mode.
Time / Date
Time and date is required for air handling unit operation planning.
Season
For the air handling unit operating in most economical mode, summer and winter seasons have been provided.
• By setting “Winter” season, unit cooling function is blocked.
• By setting “Summer” season, unit heating function is blocked.
• By setting “Auto”, automatic season selection will take place. Depending on
the heating and cooling demand, the season is selected automatically.
2.5.4.2. Personalization
In this item for the user are presented menu language, measurement units and
other control panel settings.
Reset settings
Air handling unit
Temperature control
Flow control
Time/Date
Season
Personalization
Language
English
Flow units
m
3
/h
Screen saver
On
Panel lock
Off
Touch sound