Air handling units designed for 400V AC supply voltage must be con-
nected to the stationary installation by solid cable. All units must be con-
nected through circuit breaker with 300 mA current leakage protection
(type B or B+).
Before connecting unit to the electrical power supply, it is necessary to
check whether earthing has been installed properly.
1.3. External Elements Connection
In the air handling unit it is provided connection board 1.3 a picture or 1.3 b picture (depending on the unit type),
all external elements are connected to connection board. External elements connection diagram is given in the
1.3 c picture or 1.3 d picture.
Connection Board P3
1.3 a Picture
Connection Board C3-P1
1.3 b Picture