7. Setpoint sliding
The setpoint can be shifted from -9 to +9 °C from the temperature set value at specified by user time period. To
set setpoint sliding select menu window:
8. Air quality function setting
To set the air quality (AQ) function select menu window:
“On”
– AQ function on.
“Off”
– function off.
After function is activated, the type of sensor, which is connected to the unit, is selected:
“VOC1”
(Volatile Organic Compound) – air quality sensor having signal-dependent linear relationship, the
maximum value of output signal corresponds to the highest air quality.
“VOC2”
– air quality sensor having inverse relationship, the maximum value of output signal corresponds to
lowest air quality.
RH
– relative humidity sensor.
CO
2
– carbon dioxide sensor.
Depending on the sensor type, the value of AQ function is set, according to it the intensity of the unit is regu-
lated. If actual air quality value varies from the setpoint then ventilation intensity will increase otherwise – de-
crease.
For instance, if the humidity maintaining system is designed in the device, and there is additional relative
humidity (RH) sensor, then by setting 65 % in the air quality window, and by regulating the intensity of ventila-
tion automatically, humidity of 65 % will be maintained, i.e. if humidity increases, ventilation intensity will be
increased as well, and if humidity reduces, the device will switch back to the previous mode.
This function is not provided in the units with AC fans.
9. Season setting
For the air handling unit operating in most economical mode, summer and winter seasons have been provided.
•
By setting “Winter” season, unit cooling function is blocked.
•
By setting “Summer” season, unit heating function is blocked.
•
By setting “Auto”, automatic season selection will take place. Depending on the heating and cooling de-
mand, the season is selected automatically.
To set season select menu window:
Note:
If air temperature during summer season is insufficient, air handling unit can be preset and for “Winter”
season mode, its energy expenditures will be minimal.
10. Day and time setting
For the unit proper operation in automatic mode according to preset weekly schedule the day of the week and
time should be set:
Days notation:
Mo – Monday
Fr – Friday
Tu –Tuesday
Sa – Saturday
We – Wednesday
Su – Sunday
Th – Thursday