Ducts connecting the unit to the exterior of the building must be insulated (insulation thickness
50–100 mm) to prevent condensation on cold surfaces.
•
Air intake and exhaust ducts must be fitted with air closing dampers (mechanical spring-loaded
or electric with actuators) to protect the unit from exposure to climatic conditions when the unit
is switched off.
•
In order to minimise AHU noise transferring through the ducts into ventilated areas, sound
attenuators must be connected to the unit.
•
Duct system elements must have separate brackets and to be mounted in a way that their weight
is not shifted to the unit casing.
•
The kitchen hood with integrated exhaust fan must not be connected to the additional air ex-
haust duct. Such hood must be connected to a duct separated from the general ventilation
system.
The diameter of the ducts varies by unit model:
Unit
Domekt R 200 V
Domekt R 300 F
Domekt CF 200 F
Domekt CF 200 V
Domekt CF 250 F
Domekt CF 300 V
D
uc
t diamet
er
,
mm
Duct A
125
160
160
Duct B
125
160
160
Duct C
125
160
160
Duct D
125
160
160
Duct E
125
125
–