14
UAB KOMFOVENT we reserve the right to make changes without prior notice
C6M2-19-03
EN
Temperature at AHU installation space, °C
12 14 16 18 20 22 24 26 28 30 32
80
75
70
65
60
55
50
45
40
35
30
25
20
10
5
0
-5
-10
-15
-20
-25
Patalpos, kurioje sumontuotas įrenginys, oro santykinė drėgmė,
%
Patalpos, kurioje sumontuotas įrenginys, temperatūra, °C
Lauko oro temperatūra, °C
1
2
3
Rela
tiv
e humidit
y a
t AHU installa
tion spac
e, %
O
ut
door air t
emper
atur
e, °C
Sample 1
Room temperature 20 °C
Room relative humidity 47%
Condensate will form when the
outside temperature is below +3 °C
Sample 2
Room temperature 22 °C
Outdoor temperature -5 °C
Condensate will form when the
room humidity exceeds 37 %
Sample 3
Room humidity 40%
Outdoor temperature 0 °C
Condensate will form when the
room temperature exceeds 24.5 °C
Fig. 7.
Diagram of condensate formation on the exterior surfaces of the air handling unit
Graph in Fig. 7 can be used to determine the conditions under which condensation may occur on the unit.