3.2.1. Maintenance area
When selecting the installation or mounting location of the unit, provide unrestricted and safe access to the equipment
for its repair or preventive maintenance. The inspection opening (if any) should not be less than the size of the unit and the
installation must allow easily dismantlement if necessary (e.g. in the case of complicated repairs). Minimum space for main-
tenance refers to an area free of any fixed or immovable equipment, constructions, walls, structures or furniture.
Domekt R 400 H - 600 H
Domekt CF 700 V - 700 H
30 cm
30 cm
30 cm
70 cm
10 cm
Domekt R 500 V - 700 V
30 cm
30 cm
30 cm
110 cm
10 cm
Domekt R 500 H - 700 H
30 cm
30 cm
30 cm
100 cm
10 cm
Domekt R 250 F - 400 F
Domekt R 700 F
120 cm
30 cm
30 cm
30 cm
30 cm
Fig. 5.
Minimum space for maintenance
Some DOMEKT units can be suspended on the wall, and flat units can be attached to the ceiling. It is also necessary to use
vibration absorbers for wall mounting to prevent the vibrations of the unit from being transmitted to the building structures.