6.4. Temperature Sensors Installation
The supply air temperature sensor B1 (6.4 a Picture) is mounted in the air duct in a projected place for it; after
cooler section (if provided). The minimal distance from the duct connection of the unit up to the sensor should be
not less than double diameter of the circular connection or a diagonal of rectangular connection.
The water temperature sensor B5 (6.4 b Picture) is mounted on the water pipe by screwing it into the provided
hole. The sensor must be thermo insulated!
Supply air temperature sensor B1
Water temperature sensor B5
6.4 a Picture
6.4 b Picture
6.5. Requirements for the installation of the control panel
1. The control console should be installed in a room where the following conditions are ensured:
1.1. ambient temperature: 0 ºC ... 40 ºC;
1.2. relative humidity range: 20 % ... 80 %;
1.3. protection against vertical dripping of water (IP X2).
2. Control panel connection is provided through a hole in the back or bottom side.
3. The panel can be mounted on a flush mounting box or in any other place just screwing two holes on the fastening
surface.
6.6. Control panel connection
The control panel is connected to the controller box (see Picture 6.3 a). The length of the cable for connecting
the panel with the unit may not exceed 150 m. The cable type is indicated on the electrical diagram of the unit.
Yellow (A)
( ) White
(+) Red
Green (B)
Yellow (A)
(+) Red
Green (B)
( ) White
Yellow (A)
( ) White
(+) Red
Green (B)
Yellow (A)
(+) Red
Green (B)
( ) White
6.6 Picture. Control panel connection
Control panel connection and other cable thicknesses are specified in the
wiring diagram!