EN
UAB KOMFOVENT we reserve the right to make changes without prior notice
MOU_22-10
4
Fig. 2.1
Fig. 2.2
2. OUTDOOR UNIT INSTALLATION
2.1. Outdoor Unit Installation Instructions
Step 1:
Select installation location.
The outdoor unit should be installed in the location that meets the following requirements:
•
Place the outdoor unit as close to the indoor unit as possible.
•
Ensure that there is enough room for installation and maintenance.
•
The air inlet and outlet must not be obstructed or exposed to strong wind.
•
Ensure the location of the unit will not be subject to snowdrifts, accumulation of leaves or other sea-
sonal debris. If possible, provide an awning for the unit. Ensure the awning does not obstruct airflow.
•
The installation area must be dry and well ventilated.
•
There must be enough room to install the connecting pipes and cables and to access them for main-
tenance.
•
The area must be free of combustible gases and chemicals.
•
The pipe length between the outdoor and indoor unit may not exceed the maximum allowable
pipe length.
•
If possible, DO NOT install the unit where it is exposed to direct sunlight.
•
If possible, make sure the unit is located far away from your neighbors’ property so that the noise
from the unit will not disturb them.
•
If the location is exposed to strong winds (for example: near a seaside), the unit must be placed
against the wall to shelter it from the wind. If necessary, use an awning. (See Fig. 2.1 & 2.2)
•
Install the indoor and outdoor units, cables and wires at least 1 meter from televisions or radios to
prevent static or image distortion. Depending on the radio waves, a 1 meter distance may not be
enough to eliminate all interference.