3.2. Inspection Area
Based on its type, an air handling unit may be installed indoors or outdoors. When selecting an installation or mounting
location, you must foresee sufficient and security compliant access space for repair and maintenance operations. The unit
must be installed in a way to allow partial or full disassembly and removal of assemblies out of the sections, if needed (e.g.,
in case of complex repairs).
B
≥300
≥300
A
≥B
Fig. 17.
Device inspection area
Minimum service area A defines an area which must be free of any stand-alone or immovable devices, equipment, parti-
tions, structure or furniture. This area is sufficient for performing service and filter replacement works. For repair and replace-
ment of components (e.g., removal of rotary heat exchangers), access area equal to the width of the device B shall be ensured
in front of the device.
Unit size
A, mm
B, mm
10
670
1000
20
800
1150
30
800
1300
40
800
1500
50
940
1700
60
940
1900
70
940
2100
80
940
2300
90
940
2610
Measurements in the table are approximate. For exact unit measurements see the technical data print-out.
•
When selecting an installation or mounting location, keep in mind that preventive maintenance
works must be performed at least twice a year or more often, therefore, a safe and easy access to
the unit must be foreseen.