Fire damper UVA60 M / UVA120 M installation manual 21-01
12
EN
3.
The appropriate fastenings should be
used to establish the damper onto the
supporting construction. For reference in the
hole sizes and location please use drawing of
the relevant type of the mounting collar.
For ceiling installation please be sure the collar is
places under the ceiling panel to ensure that filling
the gap with mortar is possible.
4.
When the damper is affixed to the
supporting construction, finish the mounting
process in acc. with the installation instructions.
5.
After finishing the installation process
the mounting collar can be removed and re-
used for the next fire damper installation.
Application of the mounting collar types depending on the fire damper diameter and supporting construction (wall, ceiling):
Montage collar US-d for d = [100 ÷ 315] mm
6 x Ø6 mm mounting holes
For vertical fire damper installation in the wall
Montage collar US-d for d = [355 ÷ 560] mm
6 x Ø6 mm mounting holes
For vertical fire damper installation in the wall
Filling
material
Supporting
construction
Mounting
collar