EN
Metal
stud
gypsum
plasterboard F
(EN 520) ≥ 125 mm
Mineral wool min.
100 kg/m
3
with fire
resistant coating
and additional
plasterboard pads
UVA-120M
355 ÷ 560 mm
1, 3, 4, 5
EI 60 (v
e
i↔o) S
300 Pa
Ceiling slab
Monolithic or hollow core slab
≥ 150 mm
Mortar filling
UVA-120M
100 ÷ 560 mm
2, 4, 5
EI 120 (h
o
i↔o) S
300 Pa
*
1
-
positioning of the damper: vertical;
2 - positioning of the damper: horizontal;
3 - axis position: horizontal;
4 – min. distance between casings: 200 mm;
5 – min. distance to load-bearing structural elements: 75 mm