Fire damper UVA60 M / UVA120 M installation manual 21-01
17
It is highly recommended to install the fire dampers in a way that completely prevents excess load on the dampers and transfer any load
from ducts or supporting constructions!
6.
The distance between multiple fire dampers installed close to each other shall not exceed 200 mm, as well as damper
must not be installed closer than 75 mm to the walls, ceiling or other partitions, but it is recommended to leave the access
space to actuator at least 300 mm.
The axle of the damper blade may be located only horizontally!
7.
Attach the fire damper to the supporting construction using suitable montage kit and fasteners. It is possible to re-use
these kits again.
Brackets
are used for tight holding of fire
damper when wall mounting brackets
cannot be used.
Steel overlay-type montage tool
can be
used for positioning the fire damper in the
cut-out and holding fire resistant insulation
on the ceiling.
Steel collar-type montage holders
can be
used to align the fire damper in the cut-
out by tightening it on the fire damper’s
casing and installing metal plates on a
wall.
Note: for installation of a damper into a wall axle of the blade should be positioned horizontally only! Blade of a damper always has to be
placed INSIDE the supporting construction. Main mechanism can be used as a guide to find right damper’s position: