SIA KOMFOVENT reserves the right to make changes without prior notice
Fire damper UVA60 M / UVA120 M installation manual 21-01
7
2.3.
“Dry montage” installation kit - based installation in a solid wall
Fire stopping mastic FireX (or analogue) should be applied directly to the wall around the installation opening within ≈5-10 mm from
it right before the fire damper mounting.
Dry montage kit consists of:
Two С-shape
parts –
1 set
Shield flanges made of 40 mm thick Promatect-MT fire-resistant
material
1. Fire damper UVA 120M (Ø100 ÷ 315)
2. Solid wall (aerated concrete blocks, concrete,
masonry in min. thickness 115 mm)
3. Mineral wool, min. density 40 kg/m
3
4. Fire stopping mastic FireX (or analogue)
5. Dry montage kit*
6.Mounting anchors (should be selected
accordingly to solid wall type).
* ordered separately
1
Application of the
Fire stopping mastic
around the
installation opening
EIS 60 (for size range Ø100 ÷ 315 mm)
2
2
3
5
1
5
6
6
4
Installation steps:
- prepare round installation opening D
nom
+ 30 mm
- apply fire stopping coating around the opening on the outer side of the wall surface (see picture below)
- install the damper into the opening, using appropriate fasteners
- fill the gap between the damper casing and the wall with mineral wool.
D
no
m
D
no
m
+
30
min 115