background image

SIA KOMFOVENT reserves the right to make changes without prior notice

Fire damper UVS120 H (Two-Bladed design) ∙ 

I

nstallation manual ∙ 21-01

2

CONTENT

1. FIRE DAMPER DESIGN AND DIMENSIONS 

 ....................................................................................................................................................3

2. INSTALLATION METHOD EXAMPLES 

 ...............................................................................................................................................................5

2.1. Installation in a solid wall ..................................................................................................................................................................................5

3. SAFETY REQUIREMENTS

 .........................................................................................................................................................................................6

4. INSTALLATION STEPS

 ...............................................................................................................................................................................................7

4.1. Signalling devices (switches) installation instructions for fire dampers UVS-H  .........................................................................11

5. PERIODICAL INSPECTIONS 

 ................................................................................................................................................................................13

Summary of Contents for UVS 120H

Page 1: ...EN FIRE DAMPER UVS 120H Two Bladed design Installation manual ...

Page 2: ...sign Installation manual 21 01 2 CONTENT 1 FIRE DAMPER DESIGN AND DIMENSIONS 3 2 INSTALLATION METHOD EXAMPLES 5 2 1 Installation in a solid wall 5 3 SAFETY REQUIREMENTS 6 4 INSTALLATION STEPS 7 4 1 Signalling devices switches installation instructions for fire dampers UVS H 11 5 PERIODICAL INSPECTIONS 13 ...

Page 3: ...RE DAMPER DESIGN AND DIMENSIONS 1 casing 2 blade 3 opening device with spring 4 intumescent seal 5 handle attaching screw 6 spring washer 7 handle of the opening device 8 microswitch cap 9 PUSH button mechanism replacing part 10 screw 11 Fuse element 70 The rectangular fire damper UVS120H is an emergency application type damper having two synchronously moving blades ...

Page 4: ... 500 H 540 H1 480 L 40 550 H 490 H1 430 L 65 600 H 640 H1 580 L 80 650 H 690 H1 630 L 115 700 H 740 H1 680 L 140 750 H 790 H1 730 L 165 800 H 840 H1 780 L 190 850 H 890 H1 830 L 215 900 H 940 H1 880 L 240 950 H 990 H1 930 L 265 1000 H 1040 H1 980 L 290 Bnom Hnom 200 1000 1050 A 505 B 1090 1100 A 530 B 1140 1150 A 555 B 1190 1200 A 580 B 1240 1250 A 605 B 1290 1300 A 630 B 1340 1350 A 655 B 1390 14...

Page 5: ...Two Bladed design Installation manual 21 01 5 2 1 Installation in a solid wall 2 INSTALLATION METHOD EXAMPLES EIS 90 1 Solid wall made of concrete bricks or aerated concrete blocks masonry 650 kg m minimum 115 mm thick 2 Plaster mortar e g Knauf MP75L or analogue 3 Fire damper UVS Anchor screws according wall material Opening dimension ...

Page 6: ...industrial helmet must be worn Industrial helmets protect the head against impact from objects falling from above by resisting and deflecting blows to the head Protective boots must be worn Protective boots protect the foot from falling objects or compression and prevent slipping on a slippery floor Incorrect use might cause dangerous situations It is important to correctly use the fire damper in ...

Page 7: ...stallation process any fire damper shall be inspected for damages by responsible person The installation process must include the following steps 1 Check if the blade is closing and opening without additional resistance by pressing Push button several times If sticking occurs lubricate rotation and sliding points as shown below using a suitable amount of grease 2 Please consider that fire damper h...

Page 8: ...al release mechanism In case the fuse element is melted it can be simply replaced with a new one Blade open Blade closed 4 Cover the main mechanism if delivered uncovered with plastic film or another material to protect it against clogging with construction dust and materials 5 Prepare installation opening in the wall in accordance with the prescriptions It is highly recommended to install the fir...

Page 9: ...3 52 7 54 2 55 7 57 2 58 6 60 2 61 6 63 1 64 5 66 0 850 51 5 53 1 54 7 56 2 57 8 59 2 60 9 62 6 64 1 65 6 67 1 68 7 900 53 2 54 9 56 5 58 1 59 8 61 2 63 2 65 0 66 5 68 1 69 6 71 3 950 55 0 56 7 58 4 60 2 61 9 63 3 65 5 67 3 69 0 70 6 72 2 74 0 1000 56 7 58 6 60 4 62 2 64 0 65 4 67 8 69 7 71 4 73 1 74 7 76 6 Bnom Hnom Note for installation of a damper into a wall axle of the blade should be positio...

Page 10: ...lly closed and no seizing should be observed 9 When fire damper is fully installed and verified make sure it is left in its normal working position with blade OPEN 10 Please consider that all EU working safety and Fire safety standards must be observed during the installation process 11 End position microswitches is an additional option that can be used to identify the blades position from a dista...

Page 11: ...oswitches to the indicated positions Make sure that the cam ledge pushes the microswi thes metal plate 3 Place switch cam and handle back and screw in DIN 912 screw 4 Connect microswitches to designed way Each microswitch has NC normally closed NO nor mally open and C common poles Connection scheme using signaling device Using an appropriate tool e g pliers GENTLY fold the metal plate as shown ACT...

Page 12: ... HAD BEEN DAMAGED OR SKEWED DURING INSTALLATION PROCESS THE FIRE DAMPER IS FITTED WITHOUT OBSERVING THE REQUIREMENTS OF THIS INSTRUCTION FASTENERS USED DURING INSTALLATION PROCESS BLOCK CLOSING OF THE FIRE DAMPER BLADE GAPS BETWEEN CASING OF THE FIRE DAMPER AND THE SUPPORTING CONSTRUCTION REMAIN UNFILLED THE DAMPER IS INSTALLED REMOTELY FROM THE WALL OR CEILING CONSTRUCTION WASTE OR DUST SHOULD NO...

Page 13: ...per ref No FD25 Location Kitchen 21 Damper type and size UVS90H 1200x1000 Mounted in wall w or slab s thickness W115 Access to the damper compliant Yes Installation in acc to manufacturer s instructions Yes Correct operation of the fire damper Yes Damper cleanness accumulated dust grease No Lubricate all moving Parts done not done Yes Damper condition corrosion rust No Fusible link or thermosensor...

Page 14: ...www komfovent com Fire damper UVS120 H Two Bladed design Installation manual 21 01 SIA KOMFOVENT Bukaišu iela 1 LV 1004 Riga Latvia Tel 371 24 66 4433 info lv komfovent com ...