UAB KOMFOVENT we reserve the right to make changes without prior notice
VERSO PRO2_guide_20-07
EN
5.3.5. Filter status
In this menu you can check filter impurity levels. When the contamination level reaches 100%, a message urging to
change filters is displayed. After changing the filters, delete the message to reset the contamination level.
FILTER STATUS
Extract air filter impurity
Outdoor air filter impurity
Clean filters calibration
53 %
Run
67 %
When replacing filters with filters from different manufacturers or different filtration class, calibration of clean filters is
recommended. During calibration, the unit will operate at a maximum speed for a few minutes, measure the pressure differ-
ence upstream and downstream the filter and automatically set the filtration class.
5.3.6. VAV status
This window is intended for VAV mode calibration. Calibration must be performed by a qualified specialist in accordance
with a separate “VAV Function Installation Instruction”.
VAV STATUS
VAV calibration
VAV mode
Double
Run
5.3.7. Controller status
Overview of the controller and control panel software versions.
CONTROLLER STATUS
Main module firmware
v2.340
1st zone module firmware
Control panel firmware
v1.200
Log
Download
v2.223
For detailed performance analysis, you may download a device logbook (Log) which contains weekly operation data.
To open a logbook you will need a “Log plotter” app that you can download on the “Komfovent” website. This data can be
useful in the event of a failure and may facilitate repair procedures, therefore, we recommend downloading an operation
logbook and handing it over to the authorised service personnel.