Pull the rotor completely out of the section.
Rotary heat exchangers shall be cleaned with high-
pressure washers (pressure up to 10 bar). Before washing,
the rotor motor and electronics must be additionally
protected against moisture or dismantled. Neutral or
mild alkaline detergents and disinfection agents must be
used for washing. Washing agents may be harmless to the
environment, shall not damage aluminium foil and shall be
intended for use with high-pressure washers.
12
Install the rotor housing back in the unit section only when it is completely dry.