5
COMMISSIONING
5.1
Old inverter parameter settings
Write down the old parameter settings from the DynADrive 022 frequency converter in the table below.
Table 1: DynADrive 022 parameter settings
Dip
switch
position
Switch 1
Switch 2
Switch 3
Switch 4
Switch 5
Switch 6
-1 -2 -3 -4 -1 -2 -3 -4 -1 -2 -3 -4 -1 -2 -3 -4 -1 -2 -3 -4 -1 -2 -3 -4
ON
OFF
5.2
Motor type
Record the motor type. You need to verify if you're motor is equipped with compact brake. This information is
later used on the commissioning steps. The commissioning steps are different with compact brake motors.
Motor type
Compact brake motor types
MF06MA200
MF06MA100
MF06LA200
MF06LA100
5.3
Traveling motor rating plate values
Record the traveling brake rating plate values for further use on commissioning.
Name
Motor rating plate value
Motor Nom Volt [V]
Motor Nom Freq [Hz]
Motor Nom Speed [rpm]
Motor Nom Curr [A]
Nom Magnetizing Curr [A]
Motor Cos Phi
5.4
Setting up the new inverter parameters
Compare the DIP switch settings of the DynADrive 022 with the following tables and find correct settings for
the DynA45 006 parameter settings.
1
At the DynA45 006 frequency converter; set parameter
P1.1
to value 129. This sets the engineering
password level which is needed for parameter settings.